Plan Review Notes For Permit 17120840 |
Permit Number |
17120840 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-01-17 15:09:24 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO SMOKE ALARMS ARE SHOWN ON PLANS | | | | EXISTING POOL ELECTRIC WOULD NEED TO BE BONDED TO THE | | DOORS, AND WINDOWS IF WITHIN 5" OF THE POOL. | | | | NEW OUTDOOR INSTALLATION CLEARANCES. IN OUTDOOR POOL | | AREAS, LUMINAIRES, LIGHTING OUTLETS , AND | | CEILING-SUSPENDED (PADDLE) | | FANS INSTALLED ABOVE THE POOL OR THE A REA EXTENDING | | 1.5 M | | (5 FT) HORIZONTALLY FROM THE INSIDE WALLS OF THE POOL | | SHALL BE | | INSTALLED AT A HEIGHT NOT LESS THAN 3.7 M (12 FT) ABOVE | | THE MAXIMUM | | WATER LEVEL OF THE POOL. | | | | LIGHT FIXTURES NEED TO BE MORE THAN 5' FROM THE POOL | | WATERS EDGE. | | | | |
|