Date Text
2018-01-17 15:09:24FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO SMOKE ALARMS ARE SHOWN ON PLANS
  
 EXISTING POOL ELECTRIC WOULD NEED TO BE BONDED TO THE
 DOORS, AND WINDOWS IF WITHIN 5" OF THE POOL.
  
 NEW OUTDOOR INSTALLATION CLEARANCES. IN OUTDOOR POOL
 AREAS, LUMINAIRES, LIGHTING OUTLETS , AND
 CEILING-SUSPENDED (PADDLE)
 FANS INSTALLED ABOVE THE POOL OR THE A REA EXTENDING
 1.5 M
 (5 FT) HORIZONTALLY FROM THE INSIDE WALLS OF THE POOL
 SHALL BE
 INSTALLED AT A HEIGHT NOT LESS THAN 3.7 M (12 FT) ABOVE
 THE MAXIMUM
 WATER LEVEL OF THE POOL.
  
 LIGHT FIXTURES NEED TO BE MORE THAN 5' FROM THE POOL
 WATERS EDGE.
  
  