Plan Review Notes
Plan Review Notes For Permit 17120839
Permit Number 17120839
Review Stop G
Sequence Number 3
Notes
Date Text
2018-06-27 06:45:321) EXISTING GAS PLANS ON FILE WITH THE CITY SHOW THE
 DISTANCE OF THE FARTHEST GAS OUTLET AT 59 FEET. THE 60
 FEET COLUMN IN THE GAS CODE SHALL BE USED IN THE SIZING
 OF THIS SYSTEM. 2014 FBC-FUEL GAS SEC.402.4.1.
 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 3) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE GAS PLAN NOTES THAT THE WATER HEATER INTAKE IS
 TAKING COMBUSTION AIR FROM THE GARAGE. SUBMIT
 COMBUSTION AIR CALCULATIONS. COMPLY WITH 2014 FBC-FUEL
 GAS SEC.304.5.1.
 5) THE LOCATION OF THE EXHAUST VENT SHALL CCOMPLY WITH
 THE MANUFACTURER'S INSTALLATION MANUAL AND THE 2014
 FBC-FUEL GAS CODE SEC.503.6 FOR NON-DIRECT VENT
 INSTALLATION. PROVIDE INFORMATION ON THE EXISTING VENT
 AS HEIGHT ABOVE ROOF, TYPE OF VENT MATERIAL, SIZE OF
 THE EXISTING VENT.
 6) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (F APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 7) INDICATE ON THE PLANS THAT THE RANGE AND DRYER ARE
 EXISTING.
 8) SUBMIT A SEPARATE PERMIT APPLICATION FOR THE
 INSTALLATION FOR THE GAS.
  
 NOTE: DO NOT RESUBMIT THESE DRAWINGS UNTIL A MEETING IS
 ARRANGED WITH THIS PLAN REVIEWER TO REVIEW THESE
 COMMENTS.
 UPON RESUBMITTAL, 4 TIMES THE AMOUNT OF THE PROPORTION
 OF THE FEE ATTRIBUTED TO PLANS REVIEW SHALL BE PAID PER
 FL. STATUTE 553.80 (2) (B).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  