Plan Review Notes
Plan Review Notes For Permit 17120839
Permit Number 17120839
Review Stop G
Sequence Number 2
Notes
Date Text
2018-04-03 06:34:16 
 1) YOUR PIPNG ISOMETRIC MUST INCLUDE THE ENTIRE SYSTEM.
 THERE IS A DRYER AND RANGE ON THE EXISTING SYSTEM. 2014
 FBC-FUEL GAS SECS. 402.4.1, 402.4.2, OR 2014 FBC-RES.
 SEC. G2413.
  
 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. THE PLAN NOTES COMBUSTION AIR WILL BE TAKEN
 FROM THE GARAGE BUT YOU HAVE SUBMITTED A LETTER FROM
 NAVIEN STATING COMBUSTION AIR IS OK TO BE TAKEN FROM
 THE ATTIC SPECE. CLARIFY ON THE PLAN WHERE YOU ARE
 GETTING THE COMBUSTION AIR AND PROVIDE THE REQUIRED
 CCOMBUSTION AIR CALCULATIONS. 2014 FBC- FUEL GAS SECS.
 304.1, 614.5 OR 2014 FBC-RES. SECS.2401.7 AND G2439.4.
  
 4) CITY RECORD SHOW EXISTING SYSTEM IS .5LB. INDICATE
 THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN
 PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. SEC.
 G2413.2.
  
 5) SUBMIT MANUFACTURER'S INSTALLATION MANUAL FOR ALL
 NEW GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS CODE SEC.
 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1
  
 6) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 7) IF 2 PSI SYSTEM SHOW THE LOCATION OF ALL MP
 (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 8) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 9) IF 2L PSI SYSTEM SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC SEC.410.1.
  
 10) THE PLAN SHOWS A 1/2 INCH GAS LINE FOR THE TANKLESS
 WATER HEATER BUT THE SPEC SHEETS YOU SUBMITTED SHOW A
 MINIMUM 3/4 INCH GAS CONNECTION TO THE UNIT. CLARIFY.
 THE GAS SHALL BE SIZED IN ACCORDANCE WITH THE FUEL GAS
 CODE OR 2014 FBC-RES.
  
 11) SUBMIT A SEPARATE PERMIT APPLICATION FOR THE
 INSTALLATION OF THE GAS.
  