2017-12-28 15:23:0812/28/2017 GAS 1ST REVIEW**DENIED**A SUB-GAS PERMIT IS
 REQUIRED.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 A COPY OF THE REQUIRED CHECK LIST HAS BEEN INCLUDED FOR
 YOU.
  
 1) YOUR ISOMETRIC DRAWING MUST INCLUDE THE ENTIRE
 SYSTEM. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS
 THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES
 SEC. G2413.
  
 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3
  
 4) CITY RECORD SHOW EXISTING SYSTEM IS .5LB. INDICATE
 THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN
 PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. SEC.
 G2413.2.
  
 5) SUBMIT MANUFACTURER?S INSTALLATION MANUAL FOR ALL
 NEW GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS CODE SEC.
 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1
  
 6) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? CITY RECORDS SO
 MORE THEN WATER HEATER. IF NOT, SUBMIT A COMPLETE GAS
 RISER SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE
 DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, THE BTU
 LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE
 OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. THESE
 REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM
  
 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 9) IF 2 PSI SYSTEM SHOW THE LOCATION OF ALL MP
 (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 10) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 11) IF 2L PSI SYSTEM SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC SEC.410.1.
  
  