2018-01-18 10:12:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120834
 1/18/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: PROVIDE THE FLEX DUCT SIZES.
  
 2) PROVIDE SIZING CALCULATIONS FOR THE NEW MINI SPLIT
 SYSTEM.
  
 3) VERIFY SMOKE DETECTORS ARE EXISTING AND FUNCTIONAL
 IN THE RETURN AIR PLENUM OR IN THE RETURN AIR SYSTEMS
 OF THE EXISTING RTU'S.
  
 4) M6.1: THE MIAMI-DADE NOA #13-1017.09 FOR THE ROOF
 STAND IS NO LONGER VALID. IT HAS BEEN SUPERSEDED BY
 #15-0902.05. PLEASE CORRECT AND PROVIDE TWO COPIES OF
 THE NOA WITH SHOP DRAWING APPROVAL STAMPS BY THE EOR.
  
 5) SHOW THE LOCATION OF THE NEW CONDENSER ON THE ROOF
 AND PROVIDE SITE SPECIFIC WIND LOAD DESIGN CRITERIA AND
 INSTALLATION DETAILS FOR THE STAND AND THE CONDENSER.
 THE NOA MAY BE MARKED UP TO SHOW THE APPLICABLE
 INSTALLATION DETAILS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  