Plan Review Notes For Permit 17120834 |
Permit Number |
17120834 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-01-18 10:12:50 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17120834 | | 1/18/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.1: PROVIDE THE FLEX DUCT SIZES. | | | | 2) PROVIDE SIZING CALCULATIONS FOR THE NEW MINI SPLIT | | SYSTEM. | | | | 3) VERIFY SMOKE DETECTORS ARE EXISTING AND FUNCTIONAL | | IN THE RETURN AIR PLENUM OR IN THE RETURN AIR SYSTEMS | | OF THE EXISTING RTU'S. | | | | 4) M6.1: THE MIAMI-DADE NOA #13-1017.09 FOR THE ROOF | | STAND IS NO LONGER VALID. IT HAS BEEN SUPERSEDED BY | | #15-0902.05. PLEASE CORRECT AND PROVIDE TWO COPIES OF | | THE NOA WITH SHOP DRAWING APPROVAL STAMPS BY THE EOR. | | | | 5) SHOW THE LOCATION OF THE NEW CONDENSER ON THE ROOF | | AND PROVIDE SITE SPECIFIC WIND LOAD DESIGN CRITERIA AND | | INSTALLATION DETAILS FOR THE STAND AND THE CONDENSER. | | THE NOA MAY BE MARKED UP TO SHOW THE APPLICABLE | | INSTALLATION DETAILS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|