2018-02-12 09:07:23 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE DRAINAGE PLAN THAT WAS SUBMITTED DOES NOT SHOW |
| HOW THE LOT WILL BE GRADE TO DIVERT THE SURFACE WATER |
| TO THE APPROVED POINT OF COLLECTION OR STORM DRAIN. |
| SUBMIT TWO SETS OF A SURFACE DRAINAGE PLAN. FBC-R401.3 |
| DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM |
| SEWER CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION |
| THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO |
| DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| GRADE SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN |
| THE FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, |
| FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE |
| DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE |
| SURVEY. |
| |
| 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR THE THE HORIZONTAL |
| SLIDING WINDOWS AND THE DOUBLE CASEMENT WINDOWS THAT |
| ARE SPECIFIED ON THE PLANS. |
| |
| 3) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |