Plan Review Notes
Plan Review Notes For Permit 17120819
Permit Number 17120819
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-10 19:03:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-000 THE CONSTRUCTION TYPE SHOULD BE V-B
 AND NOT R-3. R-3 IS THE TYPE OF OCCUPANCY NOT THE
 CONSTRUCTION TYPE. FBC CHAPTER 6
  
 2) SUBMIT TWO SETS OF A SURFACE DRAINAGE PLAN.
 FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
  
 3) THE SITE PLAN ON A-100 INCORRECTLY SPECIFIES THIS
 STRUCTURE AS TWO STORIES. PLEASE CORRECT. FBC 107.2.1
  
 4) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO COMPLY WITH FBC-R302.5.1.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE ROOF TILE, THE
 HORIZONTAL SLIDING WINDOWS, THE DOUBLE CASEMENT
 WINDOWS, THE DOUBLE HUNG WINDOWS AND THE IN-SWINGING
 FRENCH DOORS.
  
 6) THE PLANS SHOW IN-SWINGING GLAZED FRENCH DOORS AND
 THE PRODUCT APPROVALS THAT WERE SUBMITTED (NOA NO.
 14-0908.07) ARE FOR OUT-SWING GLAZED FRENCH DOORS. FBC
 107.3.4 SUBMIT PRODUCT APPROVALS FOR THE DOORS SHOWN ON
 THE PLANS OR REVISE THE PLANS. FBC 107.3.4
  
 7) THE PLANS SPECIFY DOUBLE HUNG WINDOWS ON SHEET
 A-200. THE PRODUCT APPROVALS THAT WERE SUBMITTED (NOA
 NO. 16-1003.01) ARE FOR SINGLE HUNG WINDOWS. SUBMIT
 PRODUCT APPROVALS FOR THE DOUBLE HUNG WINDOWS THAT ARE
 SPECIFIED ON THE PLANS OR REVISE THE PLANS.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  