Date |
Text |
2017-12-22 04:45:08 | THE SUBMITTED LETTER FROM THOMAS ENGINEERING GROUP |
| APPEARS TO BEAR A COPY OF THE ENGINEER'S SEAL AND |
| SIGNATURE. PER FLORIDA ADMINISTRATIVE CODE RULE |
| 61G15-23.001 - SIGNATURE, DATE AND SEAL SHALL BE |
| AFFIXED. |
| (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL: |
| (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS, |
| OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE |
| AND BEING FILED FOR PUBLIC RECORD; |
| THEREFORE, BOTH LETTERS FROM JASON MATTHEW GUNTHER |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE F.A.C. RULE. |
| 2) SUBMIT TWO COMPLETE COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS FOR EACH BACKFLOW DEVICE, INCLUDING THE |
| FIRE DOUBLE DETECTOR CHECK ASSEMBLY. PLACE THE |
| SPECIFICATIONS INTO SEPARATE GROUPS FOR EACH INDIVIDUAL |
| DEVICE. AS SUBMITTED AT THIS TIME, ALL THE |
| SPECIFICATION SHEETS ARE COMPILED INTO TWO GROUPS AND I |
| CANNOT DETERMINE WHICH SHEETS ARE FOR WHICH DEVICE. WPB |
| AMEND. TO FBC SEC. 107.2.1. THERE ARE NO SPECIFICATIONS |
| FOR THE 8 INCH WILKINS 350 DA, THE 3/4 INCH WILKINS 950 |
| XLD, AND ONLY ONE PAGE FOR THE WATTS 757 AND 757N. |
| 3) THE BACKFLOW DEVICES SHALL BE TESTED AND CERTIFIED |
| BY THE CITY OF WEST PALM BEACH UTILITIES DEPT.PER THE |
| CITY OF WEST PALM BEACH MANUAL FOR CROSS-CONNECTION |
| CONTROL WITH A REVISED DATE OF 9-11-17. CALL |
| 561-822-2240 FOR FURTHER INFORMATON/DDIRECTION. |
| 4) SHOW THE LOCATIONS OF ALL THE BACKFLOW PREVENTION |
| DEVICES ON THE SUBMITTED PLAN SHEET C-09. THE DEVICES |
| SHALL BE IDENTIFIED BY EITHER HIGHLIGHTING OR CLOUDING |
| THE LOCATION. WPB AMEND. TO FBC SEC. 107.2.1. SUBMIT A |
| DRAWING THAT CAN BE READ. THE PRINT ON SHT. C-09 IS SO |
| SMALL IT IS ALMOST ILLEGIBLE. WPB AMEND. TO FBC SEC. |
| 107.1, 107.2.1. |
| 5) AS NOTED IN THE COPY OF THE CORRECTION NOTICE, |
| SUBMIT BACKUP/VERIFICATION DATA AS TO HOW THE |
| CONCLUSION WAS REACHED TO ACCEPT THE SIZE OF THE |
| DEVICES THAT HAVE BEEN INSTALLED WHICH DOES NOT |
| CORRELATE WITH THE APPROVED PLANS. A PLAN REVISION |
| (AS-BUILTS) OF THE CIVIL PLANS AFFECTED BY THESE |
| CHANGES SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR |
| REVIEW AND APPROVAL PRIOR TO RECEIVING A CERTIFICATE OF |
| OCCUPANCY ON THE BUILDING. WPB AMEND. TO FBC SEC. |
| 107.4. |
| |