Plan Review Notes For Permit 17120802
Permit Number 17120802
Review Stop P
Sequence Number 2
Notes
Date Text
2018-04-17 19:10:1404/17/2018 2ND PLUMBING REVIEW**DENIED**
  
 1) BATH #1 ISOMETRIC IS STILL SHOWING 2 WET VENTED
 FIXTURES ABOVE THE UPSTREAM DRY-VENT. FBC-R P 3108.2.1
  
 2) MASTER BATHROOM TOILET IS BEING WET VENTED FROM THE
 LAUNDRY. FBC-R P3108.1 WET VENT OF BATHROOM FIXTURES
 ARE ONLY PERMITTED WITH THE BATHROOM GROUP
  
 3) ADDRESS IS REQUIRED ON THE PLAN. FBC 107.2.1
  
 4) THE FLORIDA ENERGY EFFICIENCY FORM R405-2014 IS
 CALLING OUT A 40 GALLON WATER HEATER WITH A E.F OF .92.
 AS OF APRIL 16, 2015 ALL RESDENTIAL WATER HEATER'S ARE
 REQUIRED TO BE .95 E.F UP TO 55 GALLONS. FBC- ENERGY
 CONSERVATION R 405-2017 AS DEFINED IN THE CODE OF
 FEDERAL REGULATION (CFR) 75 FR 2012.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  