Plan Review Notes For Permit 17120802 |
Permit Number |
17120802 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-04-17 13:09:11 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | 7. OK | | 8. OK | | 9. OK | | 10. | | 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED | | TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER | | CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, | | 3607.3.1 | | 12. PROVIDE LOCATION OF DISCONNECT ON PLAN. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | PHIL PETTY | | ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR | | 561-805-6742 | | [email protected] | | |
|