2018-04-20 15:24:52 | |
| |
| *****REVIEW IN PROGRESS...... NOT FINAL YET |
| |
| |
| NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| NOTE: THIS MAY BE DONE LATER WHEN THE PLANS ARE |
| APPROVED AND STAMPED BY THE CITY. |
| |
| 2- COMPLIED. |
| |
| 3- SHEET A-1. REVISE THE EGRESS WINDOWS NOTE THAT IS |
| LOCATED BELOW THE WINDOW SCHEDULE: |
| A) COMPLIED. |
| B) COMPLIED. |
| C) COMPLIED. |
| |
| 4- COMPLIED. |
| |
| 5- RESPONSE: NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 FBC-RESIDENTIAL. |
| R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| |
| 6- ROOF PLAN ON SHEET S-1: |
| A) RESPONSE: NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| SPECIFY THE CONNECTORS AT ALL ENDS OF ALL THE FRAMING |
| MEMBERS SPECIFIED ON THE FRONT PORCH AREA. COORDINATE |
| WITH DETAIL 1 ON SHEET A-3. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B) RESPONSE: NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| FRAMING OF THE OUT-LOOKERS AT THE FRONT GABLE AREA. |
| COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C) RESPONSE: NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| BEAMS AT THE REAR PORCH. THERE IS NOT PRECAST LINTEL |
| SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 7- COMPLIED. |
| |
| 8- COMPLIED. |
| |
| 9- SHEET A-2: |
| A) COMPLIED?. |
| |
| B) COMPLIED. |
| |
| C) SEMI-COMPLIED. NOTE: IF THERE IS ANY DISCREPANCY |
| BETWEEN THE REFERENCED MANUAL AND FBC AND PRODUCT |
| APPROVAL SUBMITTED, THEN FBC AND PRODUCT APPROVAL |
| PREVAILS. |
| |
| ORIGINAL COMMENT: |
| CLARIFY WHY REFERENCING "THE ARMA RESIDENTIAL ROOFING |
| MANUAL 2006". THIS STANDARD IS NOT REFERENCED IN THE |
| FLORIDA BUILDING CODE. SEE SEC. R905.2 FBC-RESIDENTIAL |
| AND REVISE AS REQUIRED. REVISE AS REQUIRED ON WALL |
| SECTIONS #5 AND #6. NOTE: REVISE DETAIL #2 ON SHEET A-3 |
| AND DETAIL #1 ON SHEET A-4 AS WELL. |
| |
| D) COMPLIED. |
| |
| 10- SECTION 5 ON SHEET S-3: |
| A) RESPONSE: NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| PROVIDE COMPLETE SPECIFICATIONS FOR THE BASE PLATE |
| FASTENERS. SPECIFY HOW MUCH EMBEDMENT IS REQUIRED. WHAT |
| DOES H.S STANDS FOR?. THERE IS NOT ABBREVIATION LEGEND. |
| NOTE: COORDINATE INFORMATION WITH STEEL COLUMN SCHEDULE |
| ON SHEET S-1, INCLUDING SIZE OF PLATE. REVISE AS |
| REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| |
| B) RESPONSE: NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| WELDING INFORMATION FOR THE STEEL COLUMN AT TOP AND |
| BOTTOM PLATES IS INCOMPLETE. ONLY THE WELDING SYMBOL IS |
| PROVIDED. PROVIDE COMPLETE SPECIFICATIONS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 11- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) COMPLIED. |
| |
| B) COMPLIED. |
| |
| C) COMPLIED. |
| |
| D) COMPLIED. |
| |
| E) COMPLIED. |
| |
| |
| |
| |
| |
| 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON |
| PLANS. |
| |
| B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| |
| C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS. |
| |
| D) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| |
| E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| |
| F) ROOF SHINGLES. |
| |
| G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS. |
| (COORDINATE WITH ITEM #9(B) ABOVE. |
| |
| H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1. |
| |
| I) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 14- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $192,608. THE |
| PERMIT FEE BALANCE IS $3,674.29. |
| |
| *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS. |
| |