2018-01-18 11:17:21 | NEW SINGLE FAMILY RESIDENCE (R3), PLUMBING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- REVISE PLUMBING RISER DIAGRAM ON SHEET P-1: |
| A) NO MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL |
| DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN |
| CONNECTION. MASTER BATHROOM AND BATHROOM #1 SHOW TWO |
| WET-VENTED FIXTURE DRAINS. (THE WATER CLOSET AND SHOWER |
| OR TUB). REVISE AS REQUIRED BY SEC. P3108.2.1 |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) PLUMBING RISER DIAGRAM IS MISSING THE DISHWASHER. |
| REVISE AS REQUIRED. SEC. P2717 FBC-RESIDENTIAL. |
| |
| C) VENTING OF THE KITCHEN SINK IS NOT CLEAR. THERE IS |
| NOT WALL BEHIND THE SINK. CLARIFY HOW THE VENTING IS |
| PROVIDED. SEC. P3104.1 FBC-RESIDENTIAL. |
| |
| D) THERE ARE TWO SINKS IN THE MASTER BATHROOM. RISER |
| ONLY SHOWS ONE. REVISE AS REQUIRED TO MATCH PLANS. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS. |
| |