Plan Review Notes
Plan Review Notes For Permit 17120802
Permit Number 17120802
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-19 10:28:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH IS A 25 AMP. PROVIDE
 CORRECTION. NEC 422.13; FBC RE3702.10
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE3609.3
 3. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE,
 INCLUDING THE GARAGE DOOR OPENER. NEC 210.8; FBC
 RE3902.2
 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING. BACK
 OF HOUSE RECEPTACLE IS MISSING, FRONT OF HOUSE IS NOT
 SHOWN AS GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8,
 210.52(E)(1) FBC RE E3901.7, E3902.3
 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4
 6. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 ALSO, THE WALL SPACING OF OUTLETS IS NOT PER CODE.
 PROVIDE CORRECTIONS. NEC 210.8, 210.52(C)(1); FBC
 RE3901.4, E3902.6
 7. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE 3703.4, 3901.6
 8. PLAN STATES THIS IS A LEVEL 2 ALTERATION, BUT
 APPLICATION STATES THIS IS A NEW HOUSE. PROVIDE
 CORRECTION. FBC 107.2.1
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED
 TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER
 CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6,
 3607.3.1
 12. PROVIDE LOCATION OF METER AND DISCONNECT ON PLAN.
 FBC 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  