2018-01-11 13:23:32 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| NOTE: THIS MAY BE DONE LATER WHEN THE PLANS ARE |
| APPROVED AND STAMPED BY THE CITY. |
| |
| 2- HORIZONTAL ROLLER EGRESS WINDOW #4 MAY NOT COMPLY |
| WITH THE MINIMUM CLEAR WIDTH OPENING REQUIRED BY SEC. |
| R310.1.3 FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE |
| MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE |
| SPECIFIED SIZE COMPLIES WITH ALL THE EGRESS |
| REQUIREMENTS. |
| |
| 3- SHEET A-1. REVISE THE EGRESS WINDOWS NOTE THAT IS |
| LOCATED BELOW THE WINDOW SCHEDULE: |
| A) WINDOWS NEED TO HAVE A MINIMUM TOTAL CLEAR OPENING |
| AREA NOT MINIMUM TOTAL GLASS AREA. SEE SEC. R310.1.1 |
| FBC-RESIDENTIAL AND REVISE WORDING AS REQUIRED. |
| |
| B) THE MINIMUM CLEAR HEIGHT IS 24" NOT 22". SEE SEC. |
| R310.1.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| |
| C) THE NET CLEAR OPENING SHALL BE MINIMUM 5.7 SQUARE |
| FEET. THE ONLY EXCEPTION IS 5.0 SQUARE FEET FOR |
| OPENINGS IN GRADE FLOOR. (NOT 4 SQUARE FEET). SEE SEC. |
| R310.1.1 FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| |
| 4- PROVIDE FIRE RESISTANCE SPECIFICATIONS FOR THE |
| INTERIOR GARAGE DOOR LEADING FROM THE GARAGE TO THE |
| MAIN HOUSE (INCLUDING THE SELF CLOSING DEVICE) AS |
| REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 FBC-RESIDENTIAL. |
| |
| 6- ROOF PLAN ON SHEET S-1: |
| A) SPECIFY THE CONNECTORS AT ALL ENDS OF ALL THE |
| FRAMING MEMBERS SPECIFIED ON THE FRONT PORCH AREA. |
| COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| FRAMING OF THE OUT-LOOKERS AT THE FRONT GABLE AREA. |
| COORDINATE WITH DETAIL 1 ON SHEET A-3. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| BEAMS AT THE REAR PORCH. THERE IS NOT PRECAST LINTEL |
| SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 7- SPECIFY ATTIC ACCESS LOCATION AND SIZE SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| |
| 8- SHEET A-0.1: PROVIDE SITE PLAN SHOWING THE |
| DIMENSIONS OF THE LOT. THERE ARE NO DIMENSIONS GIVEN. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- SHEET A-2: |
| A) WINDOW #4 SHOWN ON THE EXTERIOR ELEVATIONS DOESN'T |
| MATCH TYPE OF WINDOW SPECIFIED ON THE WINDOW SCHEDULE. |
| ELEVATIONS SHOW SINGLE HUNG WINDOWS. WINDOW #4 IS |
| HORIZONTAL ROLLER. REVISE AS REQUIRED TO MATCH TO AVOID |
| CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) CLARIFY WHICH SHINGLES UNDERLAYMENT IS GOING TO BE |
| INSTALLED. " DECK ARMOR" OR 30# UNDERLAYMENT. BOTH |
| SPECIFICATIONS ARE ON TYPICAL WALL SECTIONS #5 AND #6. |
| REVISE AS REQUIRED ON BOTH WALL SECTIONS. NOTE: REVISE |
| DETAIL #2 ON SHEET A-3 AND DETAIL #1 ON SHEET A-4 AS |
| WELL. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) CLARIFY WHY REFERENCING "THE ARMA RESIDENTIAL |
| ROOFING MANUAL 2006". THIS STANDARD IS NOT REFERENCED |
| IN THE FLORIDA BUILDING CODE. SEE SEC. R905.2 |
| FBC-RESIDENTIAL AND REVISE AS REQUIRED. REVISE AS |
| REQUIRED ON WALL SECTIONS #5 AND #6. NOTE: REVISE |
| DETAIL #2 ON SHEET A-3 AND DETAIL #1 ON SHEET A-4 AS |
| WELL. |
| |
| D) COORDINATE ROOFING PRODUCT APPROVALS LISTED ON |
| TYPICAL WALL SECTIONS #5 AND #6 WITH THOSE PRODUCT |
| APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS. SEC. |
| 107.2.1 CITY AMENDMENTS. NOTE: REVISE DETAIL #2 ON |
| SHEET A-3 AND DETAIL #1 ON SHEET A-4 AS WELL. |
| |
| 10- SECTION 5 ON SHEET S-3: |
| A) PROVIDE COMPLETE SPECIFICATIONS FOR THE BASE PLATE |
| FASTENERS. SPECIFY HOW MUCH EMBEDMENT IS REQUIRED. WHAT |
| DOES H.S STANDS FOR?. THERE IS NOT ABBREVIATION LEGEND. |
| NOTE: COORDINATE INFORMATION WITH STEEL COLUMN SCHEDULE |
| ON SHEET S-1, INCLUDING SIZE OF PLATE. REVISE AS |
| REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| B) WELDING INFORMATION FOR THE STEEL COLUMN AT TOP AND |
| BOTTOM PLATES IS INCOMPLETE. ONLY THE WELDING SYMBOL IS |
| PROVIDED. PROVIDE COMPLETE SPECIFICATIONS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 11- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 DOESN'T |
| MATCH CONDITIONED AREA SHOWN ON PLANS. REVISE AS |
| REQUIRED TO MATCH. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| B) THE NAME OF THE BUILDER IS INCORRECT. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C) PROVIDE THE NAME OF THE PERSON PREPARING THE ENERGY |
| CALCULATIONS AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY |
| CONSERVATION. |
| |
| D) ARCHITECT OF RECORD IS DESIGNING A HOUSE WITH AN |
| ATTIC VENTILATION RATIO OF 1/300. SEE SHEET A-1 AND |
| REVISE ATTIC VENT RATIO ON PAGE 2 OF 5 AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC. |
| R405.4.2 FBC-ENERGY CONSERVATION. |
| |
| 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON |
| PLANS. |
| |
| B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| |
| C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS. |
| |
| D) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| |
| E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| |
| F) ROOF SHINGLES. |
| |
| G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS. |
| (COORDINATE WITH ITEM #9(B) ABOVE. |
| |
| H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1. |
| |
| I) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 14- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $192,608. THE |
| PERMIT FEE BALANCE IS $3,674.29. |
| |
| *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE AND HELP EXPEDITE THE REVIEW PROCESS. |
| |