2018-03-22 09:48:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BUILDING CODE AND WIND CODE IS INCORRECTLY
 SPECIFIED AS FBC 6TH EDITION ON THE COVERSHEET CS-1.
 THE 2014 FBC- RESIDENTIAL APPLIES TO THIS PROJECT, THE
 2017 FBC APPLIES TO PREMITS THAT ARE APPLIED FOR AFTER
 JANUARY 1, 2018. FS CHAPTER 553
  
 2) THE TRUSS LAYOUT PLAN IS REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. FAC
 61G15-30.005 & 61G15-31.003
  
 3) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER AGENT. 2014 FBC ENERGY
 CONSERVATION SECTION R103.1.1.2 THE JURISDICTION NUMBER
 ON THE FORM IS NOT CORRECT. IT SHOULD BE 604700 AND NOT
 6047010. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS
 PROJECT.