Plan Review Notes For Permit 17120780 |
Permit Number |
17120780 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-01 14:24:22 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE DIGITAL FOLDER LABELED SOIL REPORT IS EMPTY. | | PLEASE CLARIFY. FBC 107.2.1 | | | | 2) THE PRODUCT APPROVAL NUMBER THAT IS LISTED ON SHEET | | A-3.0 FOR THE LOMANCO ROOF VENTS DOES NOT MATCH THE | | PRODUCT APPROVALS THAT WERE SUBMITTED (NOA | | NO.16-0510.28). FS 553.842 | | | | 3) THE TRUSS LAYOUT PLAN AND THE TRUSS DRAWINGS | | REFERENCE THE DESIGN CODE AS THE 2017 FBC. THE PERMIT | | WAS APPLIED FOR ON DECEMBER 20, 2017 AND THE 2014 FBC | | IS THE CODE THAT APPLIES TO THIS PROJECT. THE PLANS | | SPECIFY THE 2014 FBC. PLEASE REVISE TRUSS DOCUMENTS | | ACCORDINGLY. FS CHAPTER 553 | | | | 4) THE PERMIT VALUATION HAS BEEN INCREASED FROM | | $137,200.00 TO $166,681.00 BASED ON THE CURRENT ICC | | VALUATION DATA. FBC 109.3 | | | | 5) THE ENERGY CALCULATIONS ARE ON THE 2017 FBC FORMS | | AND THE EQUIPMENT SIZING CALCULATIONS ARE BASED ON THE | | 2017 FBC. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS | | PROJECT, THE 2017 FBC APPLIES TO PREMITS THAT ARE | | APPLIED FOR AFTER JANUARY 1, 2018. FS CHAPTER 553 |
|