2018-01-04 17:02:27 | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NEED TO SHOW EXISTING FROM NEW ELECTRICAL WORK | | | | SHOW LOCATION OF SERVICE | | | | NO LIGHTING CIRCUITS OR OUTLETS ARE SHOWN | | | | OUTLET SPACING TO BE PER CODE. | | SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | REQUIREMENTS FOR OUTLETS. | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | MEASURED HORIZONTALLY ALONG | | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET | | FROM A RECEPTACLE OUTLET. | | PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1 |
|