2018-01-04 17:02:27 
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW EXISTING FROM NEW ELECTRICAL WORK
  
 SHOW LOCATION OF SERVICE
  
 NO LIGHTING CIRCUITS OR OUTLETS ARE SHOWN
  
 OUTLET SPACING TO BE PER CODE.
 SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1