2018-01-04 14:33:30 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE VALUE OF $9,200.00 STATED ON THE REVISION |
| APPLICATION IS NOT ADEQUATE FOR THE ADDITIONAL SCOPE |
| SPECIFIED ON THE DRAWING THAT WAS SUBMITTED. PROVIDE AN |
| ITEMIZED COST BREAK DOWN FOR THE PROPOSED REVISED SCOPE |
| OF WORK WITH AN ACCURATE TOTAL VALUE. FBC 109.3 |
| BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2) SUBMIT TWO SETS OF A FLOOR PLAN THAT ACCURATELY |
| SHOWS AND DESCRIBES THE EXISTING CONDITIONS. FBC |
| 107.2.1 |
| |
| 3) THE PLANS THAT WERE SUBMITTED DO NOT MATCH THE PALM |
| BEACH COUNTY PROPERTY APPRAISER'S RECORDS. SHOW THE |
| ENTIRE STRUCTURE THAT IS UNDER ROOF ON THE PLANS |
| INCLUDING CARPORTS, PORCHES, ETC. IF THE EXISTING |
| STRUCTURE DOES NOT MATCH THE PROPERTY APPRAISER'S |
| DIAGRAM, EXPLAIN THE DIFFERENCES. FBC 107.2.1 |
| |
| 4) PROVIDE EXISTING AND PROPOSED AREA TABULATIONS ON |
| THE PLANS. FBC 107.2.1 |
| |
| 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE |
| WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR |
| DOOR TYPES. IF THE WINDOWS ARE NOT LARGE MISSILE IMPACT |
| RATED, THEN SUBMIT PRODUCT APPROVALS FOR THE STORM |
| PANELS ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE. |
| |
| 6) SHOW HOW THE BEDROOM WINDOWS WILL COMPLY WITH |
| FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. |
| BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM |
| SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND |
| RESCUE OPENING. |
| |
| FBC-R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE |
| AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR |
| OPENING OF 5.7 SQUARE FEET. EXCEPTION: GRADE FLOOR |
| OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5 |
| SQUARE FEET. |
| |
| FBC-R310.1.2 MINIMUM OPENING HEIGHT. |
| THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 |
| INCHES. |
| |
| FBC-R310.1.3 MINIMUM OPENING WIDTH. |
| THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES. |
| |
| 7) SPECIFY THE OCCUPANCY TYPE ON THE PLANS. FBC 107.2.1 |
| |
| 8) SPECIFY THE EXPOSURE CATEGORY OF THE PROJECT ON THE |
| PLANS. FBC-R301.2.1.4 |
| |
| 9) THE APPROVED PLANS WILL NEED TO BE REVIEWED BY PALM |
| BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE. |
| SEE THE IMPACT FEE REVIEW FOR DETAILS. |
| |
| 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |