2018-12-31 04:53:411) CITY RECORDS DO NOT SHOW ANY PREVIOUS GAS PERMITS
 FOR THIS ADDRESS EXCEPT THE GAS GENERATOR. GALVANIZED
 PIPE IS NOT PERMITTED UNDERGROUND PER THE 2017 FBC
 -FUEL GAS SEC.404.11. EVEN THOUGH THE GALVANIZED PIPE
 IS SHOWN AS EXISTING, IT SHALL BE REMOVED AND REPLACED
 WITH PE PIPE SINCE THERE IS NO PERMIT HISTORY ON IT.
 2) SUBMIT A SITE PLAN SHOWING OR SURVEY SHOWING THE
 LOCATION OF THE POOL HEATER AND THE EXHAUST IN RELATION
 TO OPERABLE WINDOWS, DOORS AND SOFFIT VENTS. THE
 LOCATION OF THE EXHAUST SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION MANUAL. IF IT IS NOT
 SPECIFICALLY ADDRESSED IN THE MANUAL, THE EXHAUST SHALL
 BE A MINIMUM OF 10 FT. FROM ANY BUILDING OPENING
 INCLUDING SOFFIT VENTS.
 3) SHOW THE LOCATION OF THE GAS METER ON THE REQUESTED
 SURVEY/SITE PLAN. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.3.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER. THE POOL HEATER SHALL BE LISTED AND LABELED AND
 HAVE A MINIMUM THERMAL EFFFICIENCY OF 82% PERR THE FL.
 ENERGY CODE.
 5) SHOW THE GAS OPERATING PRESSURE ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.2.
 6) INDICATE ON THE PLANS IF THE POOL HEATER IS THE ONLY
 APPLIANCE ON THIS METER/SYSTEM. IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
  