2018-05-23 07:13:4005/23/2018 PLUMBING 2ND REVIEW**DENIED**
  
 ALL OF THESE COMMENTS HAD BEEN LEFT ON-SITE WITH THE
 STOP WORK ORDER ON 04/20/2018. YOU HAVE ONLY 7 DAYS
 LEFT TO COMPLY WITH THE STOP WORK ORDER TO OBTAIN
 PERMIT WITH APPROVED INSPECTIONS.
  
 1) THE HAND SINK IS CONNECTED TO THE INTERCEPTOR AS
 REQUIRED BUT IS NOT INCLUDED ON EITHER YOUR SANITARY
 ISOMETRIC OR STANDARD-G101 DETAIL.FBC 107.2.1
  
 2) THE PIPE SIZE 2" IS UNDERSIZED AS YOU HAVE 8 DFU'S
 ON THE SYSTEM WITHT THE MAX BEING 6. FBC P 710.1 (2).
  
 3) MIN VENT SIZE IS 1 1/4"AND AAV'S ARE NOT PERMITTED
 ON ANY INTERCEPTORS. FBC P 906.1, 918.8, 1003.9
  
 4) SINKS ARE REQUIRED TO BE INDIRECTLY WASTED INTO A
 FLOOR SINK BEFOR THE INTERCEPTOR AND NOT CONNECTED
 DIRECTLY. FBC 802.1 AND HEALTH DEPT REG.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT