Plan Review Notes
Plan Review Notes For Permit 17120722
Permit Number 17120722
Review Stop P
Sequence Number 1
Notes
Date Text
2017-12-28 15:11:281) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE UNIT TO BE INSTALLED.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE UNIT. 2014
 FBC-PLUMBING SEC.1003.2, 1003.3.4.1.
 3) THE TRIPLE COMPARTMENT SHALL BE INDIRECTLY WASTED
 INTO THE GREASE UNIT. 2014 FBC-PLUMBING SEC.802.1.8.
 4) THE GREASE INTERCEPTOR SHALL BE EQUIPPED WITH A RATE
 OF FLOW CONTROL DEVICE PER 2014 FBC-PLUMBING SEC.
 1003.3.4.2.
  
 ADDITIONAL COMMENTS MAY BE GENERATED ON RESUBMITTAL OF
 REQUESTED INFORMATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW