Plan Review Notes For Permit 17120722 |
Permit Number |
17120722 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-28 15:11:28 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | AND INSTALLATION MANUAL FOR THE UNIT TO BE INSTALLED. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE UNIT. 2014 | | FBC-PLUMBING SEC.1003.2, 1003.3.4.1. | | 3) THE TRIPLE COMPARTMENT SHALL BE INDIRECTLY WASTED | | INTO THE GREASE UNIT. 2014 FBC-PLUMBING SEC.802.1.8. | | 4) THE GREASE INTERCEPTOR SHALL BE EQUIPPED WITH A RATE | | OF FLOW CONTROL DEVICE PER 2014 FBC-PLUMBING SEC. | | 1003.3.4.2. | | | | ADDITIONAL COMMENTS MAY BE GENERATED ON RESUBMITTAL OF | | REQUESTED INFORMATION. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|