Plan Review Notes
Plan Review Notes For Permit 17120719
Permit Number 17120719
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-12-21 11:47:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO DETAILS INDICATED FOR THE GENERATOR,
 SIZE, HOW IT IS FUELED, EXHAUST LOCATION, DIMENSION
 FROM THE TENT(S), HOW WILL CABLES BE PROTECTED, ETC.
  
  
  
 2) IS THIS AN EVENING EVENT AND WILL THERE BE LIGHTING.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) THERE ARE NO EMERGECNY LIGHTS INDICATED. IN THE
 EVENT THE GENERATOR FAILS HOW WILL THE EXIT AND EXIT
 PATHS REMAIN ILLUMINATED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO INDICATIONS ON HOW THIS TENT WILL BE
 HELD DOWN/SECURED.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 5) WHAT IS THE AREA INDICATED IN THE BACK OF THE TENT?
 IT PROPOSED USE? THERE ARE NO DIMENSIONS, PLEASE
 PROVIDE. WILL IT BE FENCED IN, HAVE A ROOF OVER THE
 TOP?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 6) WHAT TYPE OF HARDWARE IS ON EACH OF THE DOORS? THE
 HARDWARE SHALL COMPLY WITH THE REQUIRMENTS OF NFPA 101,
 CHAPTER12 AND CHAPTER 7.
  
 PLEASE PROVIDE DETAILS.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  