Plan Review Notes For Permit 17120719 |
Permit Number |
17120719 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-21 11:47:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO DETAILS INDICATED FOR THE GENERATOR, | | SIZE, HOW IT IS FUELED, EXHAUST LOCATION, DIMENSION | | FROM THE TENT(S), HOW WILL CABLES BE PROTECTED, ETC. | | | | | | | | 2) IS THIS AN EVENING EVENT AND WILL THERE BE LIGHTING. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 3) THERE ARE NO EMERGECNY LIGHTS INDICATED. IN THE | | EVENT THE GENERATOR FAILS HOW WILL THE EXIT AND EXIT | | PATHS REMAIN ILLUMINATED? | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 4) THERE ARE NO INDICATIONS ON HOW THIS TENT WILL BE | | HELD DOWN/SECURED. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 5) WHAT IS THE AREA INDICATED IN THE BACK OF THE TENT? | | IT PROPOSED USE? THERE ARE NO DIMENSIONS, PLEASE | | PROVIDE. WILL IT BE FENCED IN, HAVE A ROOF OVER THE | | TOP? | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 6) WHAT TYPE OF HARDWARE IS ON EACH OF THE DOORS? THE | | HARDWARE SHALL COMPLY WITH THE REQUIRMENTS OF NFPA 101, | | CHAPTER12 AND CHAPTER 7. | | | | PLEASE PROVIDE DETAILS. | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|