2017-12-20 14:43:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROVIDE THE MANUFACTURE?S SPECIFICATION CUT SHEETS
 FOR THIS INSTALLATION ON FIRE FINAL FOR FIRE INSPECTORS
 REVIEW.
  
 PER NFPA 96,
  
 11.2 INSPECTION, TESTING, AND MAINTENANCE OF
 FIRE-EXTINGUISHING SYSTEMS
  
 11.2.2* ALL ACTUATION AND CONTROL COMPONENTS, INCLUDING
 REMOTE MANUAL PULL STATIONS, MECHANICAL AND ELECTRICAL
 DEVICES, DETECTORS, AND ACTUATORS, SHALL BE TESTED FOR
 PROPER OPERATION DURING THE INSPECTION IN ACCORDANCE
 WITH THE MANUFACTURER?S
 PROCEDURES.
 11.2.3 THE SPECIFIC INSPECTION AND MAINTENANCE
 REQUIREMENTS OF THE EXTINGUISHING SYSTEM STANDARDS AS
 WELL AS THE APPLICABLE INSTALLATION AND MAINTENANCE
 MANUALS FOR THE LISTED SYSTEM AND SERVICE BULLETINS
 SHALL BE FOLLOWED.
  
 PER NFPA 17A
  
 6.4 APPROVAL OF INSTALLATIONS. THE COMPLETED SYSTEM
 SHALL BE TESTED BY TRAINED PERSONNEL AS REQUIRED BY THE
 MANUFACTURER?S LISTED INSTALLATION AND MAINTENANCE
 MANUAL.
 6.4.1 THE TESTS SHALL DETERMINE THAT THE SYSTEM HAS
 BEEN PROPERLY INSTALLED AND WILL FUNCTION AS INTENDED.
 6.4.2* WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION, THE APPROVAL TESTS SHALL INCLUDE A
 DISCHARGE TEST, IN ACCORDANCE WITH THE MANUFACTURER?S
 LISTED INSTALLATION MANUAL, TO VERIFY THAT THE SYSTEM
 IS PROPERLY INSTALLED AND FUNCTIONAL.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  