2018-01-08 14:47:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULE SHOWS THE NEW PANEL AS A MAIN LUG
 ONLY PANEL. A MAIN BREAKER IS REQUIRED IN THIS PANEL,
 OR PROVIDE A DISCONNECT AHEAD OF PANEL. PROVIDE
 CORRECTION. NEC 230.70, 230.71; FBC RE 3601.6.2, 3601.7
 2. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED
 CALCULATION DOES NOT INCLUDE BOTH AC SYSTEMS, DOES NOT
 INCLUDE ALL OF THE EQUIPMENT IN THE HOME SUCH AS ICE
 MAKER AND WINE COOLER, AND INCLUDES SOME LOADS NOT
 CORRECT SUCH AS WATER HEATER (WHICH IS NOW GAS).
 PROVIDE CORRECTION. FBC RE 3602.2
 3. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. I DO NOT SEE ANY
 CIRCUIT FOR THIS IN PANEL SCHEDULE FOR NEW BATHROOMS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  