2018-01-08 14:47:56 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PANEL SCHEDULE SHOWS THE NEW PANEL AS A MAIN LUG |
| ONLY PANEL. A MAIN BREAKER IS REQUIRED IN THIS PANEL, |
| OR PROVIDE A DISCONNECT AHEAD OF PANEL. PROVIDE |
| CORRECTION. NEC 230.70, 230.71; FBC RE 3601.6.2, 3601.7 |
| 2. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED |
| CALCULATION DOES NOT INCLUDE BOTH AC SYSTEMS, DOES NOT |
| INCLUDE ALL OF THE EQUIPMENT IN THE HOME SUCH AS ICE |
| MAKER AND WINE COOLER, AND INCLUDES SOME LOADS NOT |
| CORRECT SUCH AS WATER HEATER (WHICH IS NOW GAS). |
| PROVIDE CORRECTION. FBC RE 3602.2 |
| 3. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH |
| LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING |
| ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 |
| 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. I DO NOT SEE ANY |
| CIRCUIT FOR THIS IN PANEL SCHEDULE FOR NEW BATHROOMS. |
| PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4 |
| 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |