Text |
2017-12-15 13:19:23 | DENIED |
| |
| YOUR DEVICE DOES NOT MEET THE CROSS CONNECTION STANDS |
| SET BY WPB. |
| |
| ALL BACKFLOW DEVICES MUST BE LEAD FREE. LEAD FREE (LF) |
| SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED ON |
| THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN |
| ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL |
| NOT BE APPROVED. |
| |
| ALL BACKFLOW PREVENTION ASSEMBLIES SHALL BE INSTALLED |
| BY A CERTIFIED BACKFLOW PREVENTER TESTER/REPAIRER. THE |
| CERTIFIED BACKFLOW PREVENTER TESTER/REPAIRERS IS |
| RESPONSIBLE TO MAKE SURE THE ASSEMBLY IS WORKING |
| PROPERLY WHEN IT IS INSTALLED, AND TO MAKE AVAILABLE |
| ALL INSTALLATION AND TESTING INFORMATION FOR APPROVAL |
| BY THE DIRECTOR OR DESIGNEE. |
| |
| CERTIFIED BACKFLOW TESTERS/REPAIRERS |
| |
| CERTIFICATION REQUIREMENTS: ALL INDIVIDUALS OR |
| COMPANIES DESIRING TO: INSTALL, TEST, REPAIR, OVERHAUL, |
| OR MAINTAIN BACKFLOW PREVENTION ASSEMBLIES WITHIN THE |
| CITY OF WEST PALM BEACH UTILITIES SERVICE AREA, MUST |
| SUBMIT THE FOLLOWING CURRENT DOCUMENTS TO THE |
| DEPARTMENT OF PUBLIC UTILITIES IN ORDER TO BE A CITY |
| CERTIFIED BACKFLOW PREVENTER TESTER/REPAIRER: |
| |
| O CERTIFIED PLUMBING CONTRACTOR ? STATE OF FLORIDA |
| OCCUPATIONAL LICENSE |
| O COUNTY OR CITY LOCAL BUSINESS TAX RECEIPT FROM WHERE |
| THE BUSINESS ORIGINATES (IF NOT IN WEST PALM BEACH, |
| MUST REGISTER AS A CONTRACTOR WITH THE CITY OF WEST |
| PALM BEACH, CONSTRUCTION SERVICES, OCCUPATIONAL LICENSE |
| DEPARTMENT) |
| O BACKFLOW PREVENTION ASSEMBLY TESTER CERTIFICATION FOR |
| EACH TESTER |
| O BACKFLOW PREVENTION ASSEMBLY REPAIR CERTIFICATION FOR |
| EACH TESTER |
| O ANNUAL TESTING KIT CALIBRATION REPORT/CERTIFICATION |
| FOR EACH TESTING KIT THAT WILL BE USED BY THE CERTIFIED |
| BACKFLOW PREVENTER TESTER/REPAIRER |
| |
| PLEASE PROVIDE PLUMBING CONTRACTOR INFORMATION ON |
| RE-SUBMITTAL |
| |