2017-12-18 10:06:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) TEST TO ENSURE THE FOLLOWING IS COMPLIANT INCLUDING, |
| BUT NOT LIMITED TO, DBA AT THE PILLOW HEIGHT. |
| |
| |
| 14.4.1.2* REACCEPTANCE TESTING. |
| 14.4.1.2.1 REACCEPTANCE TESTING SHALL BE PERFORMED AS |
| REQUIRED IN 14.4.1.2.1.1 THROUGH 14.4.1.2.1.4. |
| 14.4.1.2.1.1 WHEN AN INITIATING DEVICE, NOTIFICATION |
| APPLIANCE, OR CONTROL RELAY IS ADDED, IT SHALL BE |
| FUNCTIONALLY TESTED. |
| 14.4.1.2.1.2 WHEN AN INITIATING DEVICE, NOTIFICATION |
| APPLIANCE, OR CONTROL RELAY IS DELETED, ANOTHER DEVICE, |
| APPLIANCE, OR CONTROL RELAY ON THE CIRCUIT SHALL BE |
| OPERATED. |
| 14.4.1.2.1.3 WHEN MODIFICATIONS OR REPAIRS TO CONTROL |
| EQUIPMENT HARDWARE ARE MADE, THE CONTROL EQUIPMENT |
| SHALL BE TESTED IN ACCORDANCE WITH TABLE 14.4.2.2, |
| ITEMS 1(A) AND 1(D). |
| 14.4.1.2.1.4 WHEN CHANGES ARE MADE TO SITE-SPECIFIC |
| SOFTWARE, THE FOLLOWING SHALL APPLY: |
| (1) ALL FUNCTIONS KNOWN TO BE AFFECTED BY THE CHANGE, |
| OR IDENTIFIED BY A MEANS THAT INDICATES CHANGES, SHALL |
| BE 100 PERCENT TESTED. |
| (2) IN ADDITION, 10 PERCENT OF INITIATING DEVICES THAT |
| ARE NOTDIRECTLY AFFECTED BY THE CHANGE, UP TO A MAXIMUM |
| OF 50 DEVICES, ALSO SHALL BE TESTED AND CORRECT SYSTEM |
| OPERATION SHALL BE VERIFIED. |
| (3) AREVISED RECORD OF COMPLETION IN ACCORDANCE WITH |
| 10.18.2.1 SHALL BE PREPARED TO REFLECT THESE CHANGES. |
| 14.4.1.2.2 CHANGES TO ALL CONTROL UNITS CONNECTED OR |
| CONTROLLED BY THE SYSTEM EXECUTIVE SOFTWARE SHALL |
| REQUIRE A 10 PERCENT FUNCTIONAL TEST OF THE SYSTEM, |
| INCLUDING A TEST OF AT LEAST ONE DEVICE ON EACH INPUT |
| AND OUTPUT CIRCUIT TO VERIFY CRITICAL SYSTEM FUNCTIONS |
| SUCH AS NOTIFICATION APPLIANCES, CONTROL FUNCTIONS, AND |
| OFF-PREMISES REPORTING. |
| 14.4.2* TEST METHODS. |
| 14.4.2.1* AT THE REQUEST OF THE AUTHORITY HAVING |
| JURISDICTION, THE CENTRAL STATION FACILITY INSTALLATION |
| SHALL BE INSPECTED FOR COMPLETE INFORMATION REGARDING |
| THE CENTRAL STATION SYSTEM, INCLUDING SPECIFICATIONS, |
| WIRING DIAGRAMS, AND FLOOR PLANS THAT HAVE BEEN |
| SUBMITTED FOR APPROVAL PRIOR TO INSTALLATION OF |
| EQUIPMENT AND WIRING. |
| 14.4.2.2* SYSTEMS AND ASSOCIATED EQUIPMENT SHALL BE |
| TESTED ACCORDING TO TABLE 14.4.2.2. |
| |
| |
| |