Plan Review Notes
Plan Review Notes For Permit 17120551
Permit Number 17120551
Review Stop M
Sequence Number 3
Notes
Date Text
2018-06-26 14:35:283RD REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120551
 6/26/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: AS NOTED IN THE PREVIOUS REVIEW,
 MECHANICAL VENTILATION IS REQUIRED FOR THE BATHROOMS IN
 ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL. THIS IS
 A COMMERCIAL R2 OCCUPANCY, NOT A SINGLE FAMILY R3
 OCCUPANCY WHERE NATURAL VENTILATION OF BATHROOMS IS
 ALLOWED PER THE FBC-14 RESIDENTIAL. PLEASE REVIEW THE
 FOLLOWING CODES THAT ARE ALSO APPLICABLE TO THE
 PROPOSED PROJECT:
  
 A) SECTION 1011.1 FBC-14 EXISTING BUILDING WHICH STATES
 A CHANGE OF OCCUPANCY SHALL HAVE LIGHT AND VENTILATION
 IN COMPLIANCE WITH THE FLORIDA BUILDING CODE.
  
 B) SECTION 1203.4.2.1 FBC-14 BUILDING WHICH STATES
 BATHROOMS SHALL BE "MECHANICALLY VENTILATED".
  
 2) M1: THE MODEL NUMBER AEE12DT LISTED IN SCHEDULE IS
 NOT A FRIDGIDAIRE MODEL NUMBER. IT IS A GE NUMBER-
 PLEASE CORRECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  