Plan Review Notes
Plan Review Notes For Permit 17120550
Permit Number 17120550
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-24 12:44:172ND REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120550
 4/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS #2, 3, & 4 FROM THE 1ST REVIEW STILL EXIST.
 I HAVE PRINTED THEM BELOW WITH SOME ADDITIONAL NOTES-
 PLEASE COMPLY.
  
 2) SPACE HEATING SYSTEMS ARE REQUIRED FOR THE SUITES
 PER SECTION 309.1 FBC -14 MECHANICAL. PLEASE INDICATE
 HOW COMPLIANCE IS BEING MET. (THE NEW AC EQUIPMENT
 SCHEDULE ON THE M1 PLAN DOESN'T INDICATE IF THE SYSTEMS
 PROVIDE HEAT, AND NO CUT SHEETS FOR THE SYSTEMS HAVE
 BEEN PROVIDED FOR CLARIFICATION).
  
 3) VENTILATION IS REQUIRED FOR THE SUITES- EITHER
 NATURALLY OR MECHANICALLY- PER SECTION 401.2. PLEASE
 INDICATE HOW COMPLIANCE IS BEING MET. (THE PLAN APPEARS
 TO SHOW NATURAL VENTILATION. PLEASE SEE SECTION 402.2
 AN PROVIDE CALCULATIONS TO INDICATE COMPLIANCE).
  
 4) EXHAUST VENTILATION SYSTEMS ARE REQUIRED FOR BOTH
 THE KITCHENS AND THE BATHROOMS PER TABLE 403.3.
 INDICATE HOW COMPLIANCE IS BEING MET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  