Plan Review Notes
Plan Review Notes For Permit 17120550
Permit Number 17120550
Review Stop B
Sequence Number 2
Notes
Date Text
2018-04-30 08:26:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SCOPE NOT CLEAR. PLANS STATE THAT ALL
 EXISTING FINISHES ARE TO REMAIN. APPLICATION STATES
 THAT CABINETS WILL BE INSTALLED.
  
 2. FBC 107, SCOPE NOT CLEAR. APPLICATION STATES THAT 2
 ADA BATHROOMS WILL BE INSTALLED. PLANS STATE ALL
 EXISTING FINISHES WILL REMAIN. ADA (FBC ACCESSIBILITY)
 IS APPLICABLE TO PLACES OF PUBLIC ACCOMMODATION.
 ARCHITECTURAL SHEETS NOT CLEAR AS TO WHERE THE TWO ADA
 BATHROOMS ARE PROPOSED.
  
 3. FBC 107, SCOPE NOT CLEAR. I WAS TOLD THAT THIS IS A
 CHANGE OF OCCUPANCY, BUT I WAS UNABLE TO LOCATE THIS
 INFOROMATION ON THE PLANS. FBC EXISTING BUILDING
 1001.2, PROVIDE A CODE SUMMARY - EXISTING OCCUPANCY,
 PROPOSED NEW OCCUPANCY. SHOW COMPLIANCE WITH ALL
 REQUIREMENTS. A COMPLETE REVIEW CANNOT BE DONE AT THIS
 TIME DUE TO LACK OF INFORMATION.
  
 4. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY MAY BE
 REQUIRED. 561-233-5025 FOR MORE INFORMATION.
  
 5. SEE ADDRESS REVIEW; PLANS NEED TO BE REVISED TO
 REFLECT CORRECT ADDRESSES AND UNIT NUMBERS.
  
 6. FBC 109, PROVIDE A COST BREAKDOWN FOR ALL WORK
 PROPOSED.
  
 7. A RESPONSE LETTER WOULD BE HELPFUL. NO LETTER WAS
 PROVIDED. NOT CLEAR ON PLANS HOW PREVIOUS COMMENTS WERE
 ADDRESSED.
  