Plan Review Notes
Plan Review Notes For Permit 17120550
Permit Number 17120550
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-10 08:26:301ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT.A-4 AND A-5 PLEASE SHOW GRAB BARS TO BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC PL 609.4
  
 2. SHOW DIMENSIONS FOR FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
 3. PLEASE SHOW HOT AND COLD AND LABEL PIPING ON WATER
 RISER. PER WPB AMEND TO FBC 107.2.1
  
 4. BECAUSE OF THE AGE OF THE BUILDING AND THIS BEING A
 CHANGE OF OCCUPANCY THE SAFETY PIPING ON THE WATER
 HEATER WILL NEED TO BE BROUGHT UP TO CODE, THE T+P
 RELIEF VALVE AND DRAIN LINE AND THERMAL EXPANSION. PER
 FBC PL CH 504 AND 607.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  