Plan Review Notes For Permit 17120526 |
Permit Number |
17120526 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-15 15:34:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER SHOWS #2 PANEL SCHEDULE SHOWS #1 | | | | ONLY ONE SET OF FLOOR PLAN DRAWINGS. | | | | PLEASE INDICATE TYPE OF WIRE USED COPPER OR ALUMINUM | | | | PROVIDE LOAD CALCULATION FOR THE RISER UP TO FPL.. | | | | |
|