Plan Review Notes For Permit 17120517 |
Permit Number |
17120517 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-02-15 15:08:35 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17120517 | | 2/15/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-1: PLEASE CORRECT THE NOTE THAT IS EXCLUDING | | COMPLIANCE WITH THE FL. ENERGY CONSERVATION CODE- 2014. | | THE PROPOSED PROJECT IS NOT A RENOVATION, IT IS A | | CHANGE OF OCCUPANCY. REFER TO SECTION C101.4.4 AND | | SUBMIT AN ENERGY COMPLIANCE REPORT. | | | | 2) M-1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION | | OF THE NEW ROOFTOP FAN- SECTION 301.15 FBC-14 | | MECHANICAL. SUBMIT A FL. PRODUCT APPROVAL AND/OR | | MIAMI-DADE NOA FOR THE FAN IF APPLICABLE. | | | | 3) M-1: IT APPEARS BOTH OPTIONS- ITEM #1 AND ITEM #2 - | | ARE TO BE USED TO AUTOMATICALLY CONTROL THE OPERRATION | | OF THE GARAGE EXHAUST FAN. PLEASE SEE SECTION 404.1 AND | | CHOOSE EITHER ITEM #1 OR #2, AND PROVIDE DETAILS AND | | SUBMITTALS FOR THE SENSORS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|