Plan Review Notes
Plan Review Notes For Permit 17120517
Permit Number 17120517
Review Stop M
Sequence Number 2
Notes
Date Text
2018-02-15 15:08:352ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120517
 2/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE CORRECT THE NOTE THAT IS EXCLUDING
 COMPLIANCE WITH THE FL. ENERGY CONSERVATION CODE- 2014.
 THE PROPOSED PROJECT IS NOT A RENOVATION, IT IS A
 CHANGE OF OCCUPANCY. REFER TO SECTION C101.4.4 AND
 SUBMIT AN ENERGY COMPLIANCE REPORT.
  
 2) M-1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE NEW ROOFTOP FAN- SECTION 301.15 FBC-14
 MECHANICAL. SUBMIT A FL. PRODUCT APPROVAL AND/OR
 MIAMI-DADE NOA FOR THE FAN IF APPLICABLE.
  
 3) M-1: IT APPEARS BOTH OPTIONS- ITEM #1 AND ITEM #2 -
 ARE TO BE USED TO AUTOMATICALLY CONTROL THE OPERRATION
 OF THE GARAGE EXHAUST FAN. PLEASE SEE SECTION 404.1 AND
 CHOOSE EITHER ITEM #1 OR #2, AND PROVIDE DETAILS AND
 SUBMITTALS FOR THE SENSORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  