2018-02-20 10:40:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. RISER DIAGRAM SHOWS THE 600 AMP MAIN PANEL BEING FED
 WITH THREE 3/0 CONDUCTORS. CONDUCTOR SIZE 3/0 IS NOT
 RATED FOR 600 AMPS. ALSO, THIS IS SHOWN AS A 3 PHASE
 SERVICE, WHICH WOULD REQUIRE 4 WIRES FROM POWER
 COMPANY. AN EGC (EQUIPMENT GROUNDING CONDUCTOR) WOULD
 NOT BE INSTALLED IN THIS CONDUIT. PROVIDE CORRECTIONS
 NEC 310.15(B)(16), 250.6; FBC 107.2.1 (RISER NOW SHOWS
 (4) 1000 KCMIL WIRES IN A 3" CONDUIT. THIS QUANTITY AND
 SIZE OF WIRE WILL NOT FIT IN A 3" CONDUIT PER CODE.
 PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C)
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED AS STATED IN LETTER)
 5. CORRECTED.
 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. THIS SHOULD BE EXPRESSED IN LIGHT FIXTURE WATTAGE
 IN RELATION TO SQUARE FOOT WATTAGE PERMITTED. IT HAS
 NOTHING TO DO WITH THE AMPACITY OF THE CIRCUIT FEEDING
 THE LIGHTING. FBC EC 405.5.2 (NOT PROVIDED. THIS
 CHART/GRAPH SHOULD INDICATE THE AMOUNT OF WATTAGE
 ALLOWED FOR THE SPACE AND THE AMOUNT DESIGNED FOR THE
 SPACE MEETING CODE REQUIREMENTS.)
 7. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 (NOT
 PROVIDED AS STATED IN LETTER)
 8. CORRECTED.
 9. COMPLIED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  