2018-02-20 10:40:55 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS |
| REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. RISER DIAGRAM SHOWS THE 600 AMP MAIN PANEL BEING FED |
| WITH THREE 3/0 CONDUCTORS. CONDUCTOR SIZE 3/0 IS NOT |
| RATED FOR 600 AMPS. ALSO, THIS IS SHOWN AS A 3 PHASE |
| SERVICE, WHICH WOULD REQUIRE 4 WIRES FROM POWER |
| COMPANY. AN EGC (EQUIPMENT GROUNDING CONDUCTOR) WOULD |
| NOT BE INSTALLED IN THIS CONDUIT. PROVIDE CORRECTIONS |
| NEC 310.15(B)(16), 250.6; FBC 107.2.1 (RISER NOW SHOWS |
| (4) 1000 KCMIL WIRES IN A 3" CONDUIT. THIS QUANTITY AND |
| SIZE OF WIRE WILL NOT FIT IN A 3" CONDUIT PER CODE. |
| PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C) |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 (NOT PROVIDED AS STATED IN LETTER) |
| 5. CORRECTED. |
| 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| CODE. THIS SHOULD BE EXPRESSED IN LIGHT FIXTURE WATTAGE |
| IN RELATION TO SQUARE FOOT WATTAGE PERMITTED. IT HAS |
| NOTHING TO DO WITH THE AMPACITY OF THE CIRCUIT FEEDING |
| THE LIGHTING. FBC EC 405.5.2 (NOT PROVIDED. THIS |
| CHART/GRAPH SHOULD INDICATE THE AMOUNT OF WATTAGE |
| ALLOWED FOR THE SPACE AND THE AMOUNT DESIGNED FOR THE |
| SPACE MEETING CODE REQUIREMENTS.) |
| 7. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 (NOT |
| PROVIDED AS STATED IN LETTER) |
| 8. CORRECTED. |
| 9. COMPLIED. |
| 10. CORRECTED. |
| 11. CORRECTED. |
| 12. CORRECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |