Plan Review Notes
Plan Review Notes For Permit 17120517
Permit Number 17120517
Review Stop B
Sequence Number 2
Notes
Date Text
2018-02-13 13:21:162014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120517/ CHANGE OF OCCUPANCY
 ADD: 925/ 1013 N. RAILROAD AVE. (PCN:
 74-43-43-15-20-005-0110)
 CONT: FLORIDA GENERAL CONTRACTOR
 TEL: 561-704-5042
 E-MAIL: JIG3684@ YAHOO.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 13/ 2018
 ACTION: DENIED
  
 1, 2A & 2D) THE SITE PLAN C-1 IS CORRECT IN THE
 PLACEMENT OF THE PROPERTY LINE BETWEEN 925 N. RAILROAD
 AVE. & 1013 N. RAILROAD AVE. THE SHEET A-1 SHOWS WHAT
 APPEARS A 4 HOUR WALL BETWEEN PROPERTIES OWNED BY THE
 SAME OWNER WITH OPENINGS IN THE FIRE WALL. I CANNOT
 FIND WHERE THERE WAS A PERMIT PULLED FOR THE CURRENT
 CONFIGURATION OF WALLS (FIREWALL). IN 1998 UNDER
 98007817 THIS SPACE WAS A BAKERY AND WHERE THE 4 HOUR
 FIRE WALL STANDS THERE WAS A VERY LARGE PROOF ROOM.
 I?VE SPOKEN WITH THE ARCHITECT NADER GOUBRAN ABOUT THE
 FIRE WALL. HE INDICATED THE LAWYER FOR HIS CLIENT WAS
 SUPPOSED TO HAVE FILED A UNITY OF TITLE, THIS WILL NEED
 TO BE VERIFIED THROUGH THE CITY SURVEYOR VINCE NOEL.
  
 3) COMPLIED. SHEET C1. THE 2014 FLORIDA BUILDING CODE
 AND EXISTING BUILDING CODE .
  
 4) SHEET A2 EXISTING AND DEMOLITION PLAN:
 2014 FBC-EXISTING BUILDING CODE 1001.3 CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP.
  
 CREATION OR EXTENSION OF NONCONFORMITY.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 4A) SHEET A2 EXISTING AND DEMOLITION PLAN. THE BUILDING
 1013 N. RAILROAD AVE. IN 1998 WAS A BAKERY, WHERE THE
 NOW EXISTING 4 HR. FIRE WALL IS LOCATED THERE WAS NO
 FIRE WALL BATHROOMS EXISTED AND A VERY LARGE PROOF
 ROOM., PERMIT 98007817 (SEE FILE-NET) DID NOT TRANSFER
 OVER WHEN WE WENT TO COMMUNITY PLUS.
  
 4B) SHEET A1 AND A2 EXISTING AND DEMOLITION PLAN. ON
 THE WEST SIDE OF THE BUILDING A EXISTING CORRIDOR.
 PALM BEACH COUNTY AERIAL PHOTOGRAPHY SHOWS FROM
 2009-2014 THIS AREA BEING A OPEN AIR LOADING PLATFORM.
 IN JAN. 31/2016 THIS AREA HAS BEEN ENCLOSED ON THE
 NORTH AND WEST WITH A WALL AND A ROOF FRAMING AND
 ROOFING SYSTEM BUILT WITHOUT THE BENEFIT OF PERMIT AND
 INSPECTIONS.
  
 4C) PICTURES TAKEN ON LINE FROM THE DANIEL ART WORLD
 GALLERIE SHOW NEW STOREFRONT SYSTEM, DOORS SIDELIGHTS,
 MULLIONS AND TRANSOM INSTALLED WITHOUT THE BENEFIT OF
 PERMIT.
  
 5) CORRECTED STATEMENT. THE COVERSHEET CORRECTLY
 ILLUSTRATES WHERE THE PROPERTY LINE IS BETWEEN 925 N.
 RAILROAD AVE. AND 1013 N. RAILROAD AVE. EITHER THE 4
 HOUR FIRE WALL WILL NEED TO BE MADE LEGAL OR A UNITY OF
 TITLE. I?VE SPOKEN WITH THE ARCHITECT NADER GOUBRAN
 ABOUT THE FIRE WALL. HE INDICATED THE LAWYER FOR HIS
 CLIENT WAS SUPPOSED TO HAVE FILED A UNITY OF TITLE;
 THIS WILL NEED TO BE VERIFIED THROUGH THE CITY SURVEYOR
 VINCE NOEL. TO DATE VINCE NOEL HAS NOT RETURNED MY
 PHONE CALL.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
  
 6) SEMI-COMPLIED. NETHER SHEET A-1 NOR A-2 PROVIDE WHAT
 IS EXISTING AND WHAT IS NEW. PLEASE BE ADVISED GOOGLE
 STREET VIEW IN FEB. OF 2015 SHOWS THE 4 LOADING BAYS
 OPEN ALONG N. RAILROAD AVE. FOR 925 AND 1013 N.
 RAILROAD AVE. WITHIN THE LOADING BAYS THERE IS ONLY ONE
 EXISTING SET OF STAIR AND NO GUARDRAILS. THE OTHER
 ISSUE IS HOW THE BUILDINGS ARE BUILT BETWEEN 925 AND
 1013 N. RAILROAD AVE. THERE WOULD HAVE BEEN A 4 HOUR
 FIRE WALL SEPARATING THE BUILDINGS, WE DO NOT HAVE
 PERMITS PULLED CREATING OPENINGS WITHIN THE 4 HOUR FIRE
 WALL NOR HOW THE STRUCTURE ABOVE IS BEING SUPPORTED? IT
 WOULD APPEAR THERE HAS BEEN A LOT OF WORK ALREADY
 COMPLETED WITHOUT THE BENEFIT OF A PERMIT. A THOROUGH
 REVIEW CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW. WORK
 COMPLETED WITHOUT THE BENEFIT OF A PERMIT MAY ALSO
 RESULT IN A 4X FEE FOR THE WORK NOT PERMITTED.
  
 7) 2ND REQUEST. SHEET A-1 SHOWS THE EXIT ACCESS PATHS
 THROUGHOUT THE BUILDING BUT THE TRAVEL DISTANCE FOR
 EACH ROUTE HAS NOT BEEN INDICATED ON THE PLANS, PLEASE
 SHOW COMPLIANCE WITH 2014 FBC-B TABLE 1016.2.
  
 THE DESIGNER OF RECORD HAD INDICATED ON SHEET A1, THE
 LIFE SAFETY PLAN THAT THERE ARE 4 EXITS FROM THE
 BUILDING AND 3 ACCESSIBLE, NOT TRUE, THERE IS ONLY 1
 EXIT FROM THE BUILDING AND 1 ACCESSIBLE EXIT WITH THE
 EXTERIOR RAMP. ON THE WEST SIDE OF THE ART MERCANTILE
 AREA THERE ARE 2 NEW EXIT DOORS SHOWN ON THE PLAN AND
 LEADING TO THE EXISTING CORRIDOR. NEVER PERMITTED WILL
 NEED TO BE MADE LEGAL OR REMOVED.
 THE SECOND ISSUE WITH USING THIS SPACE EITHER AS A EXIT
 ACCESS CORRIDOR OR A EXIT PASSAGE WAY IS IT IS NOT
 ENCLOSED AT THE END, IT LEADS FROM THE INSIDE TO THE
 EXTERIOR WITHOUT A DOOR.
 THE WORST PROBLEM WITH THIS IS THE NEW EXIT CORRIDOR
 LEADS YOU RIGHT BACK TO THE MAIN ENTRY/ EGRESS, THERE
 IS NO REMOTENESS AS REQUIRED UNDER ;
 2014 FBC-B 1015.2.1. WHERE TWO EXITS OR EXIT ACCESS
 DOORWAYS ARE REQUIRED FROM ANY PORTION OF THE EXIT
 ACCESS, THE EXIT DOORS OR EXIT ACCESS DOORWAYS SHALL BE
 PLACED A DISTANCE APART EQUAL TO NOT LESS THAN ONE-HALF
 OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDING OR AREA TO BE SERVED MEASURED IN A
 STRAIGHT LINE BETWEEN EXIT DOORS OR EXIT ACCESS
 DOORWAYS.
 SHEET A1 I MEASURES FROM THE SOUTHEAST CORNER TO THE
 NORTHWEST CORNER IN MILLIMETERS. THE OVER ALL
 MEASUREMENT WAS 420 MM. THE 2 WEST DOORWAYS DO NOT MEET
 THE REMOTENESS BECAUSE THEY LEAD YOU BACK TO THE MAIN
 ENTRY. THE ONLY OTHER EXIT IS FOUND ON THE EAST SIDE OF
 THE BUILDING WITH A NEW RECESSED EXIT DOOR TO THE
 EXTERIOR. SINCE THIS IS A NON- SPRINKLERED BUILDING WE
 USE ? OF THE OVERALL DIAGONAL OR 210 MM TO DETERMINE
 REMOTENESS. MEASURED FROM THE CENTERLINE OF THE DOUBLE
 DOORS SOUTH EXPOSURE TO THE NEW PROPOSED DOORWAY IT IS
 ONLY 180 MM AWAY, THIS LOCATION DOES NOT MEET THE
 REMOTENESS TEST.
 WITH THE DOORWAY NOT MEETING THE REMOTENESS TEST THE
 ACCESSIBLE LULA LIFT CAN NOT BE COUNTED AS AN
 ACCESSIBLE EXIT.
  
 8) 2ND REQUEST. THE COVERSHEET INDICATES THE OCCUPANT
 LOAD OF 378 AND SHEET A-1 SHOWS 4 EXITS AND 3
 ACCESSIBLE EXIT. PLEASE REVIEW SECTION:
 4 X 0.60= 2.4, REQUIRES 3 ACCESSIBLE EXITS THAT WILL
 MEET THE REMOTENESS REQUIREMENTS UNDER FBC-B 1015.2.1.
  
 2014 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 2014 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404.
  
 (GRAY BOX FLORIDA SPECIFIC). BARRIERS AT COMMON OR
 EMERGENCY ENTRANCES AND EXITS OF BUSINESS
 ESTABLISHMENTS CONDUCTING BUSINESS WITH THE GENERAL
 PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION, OR UNDER
 CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT A PERSON
 FROM USING SUCH ENTRANCES OR EXITS SHALL BE REMOVED.
  
 9) 2ND REQUEST. SHEET A-1 INDICATES THE USE OF (2) NEW
 LIFTS, PLEASE BE MORE SPECIFIC, TO BE LIMITED USE/
 LIMITED- APPLICATION UNDER SECTION 408 OF THE
 ACCESSIBILITY CODE COMPLYING WITH ASME A17.1 OR
 PLATFORM LIFTS UNDER SECTION 410 OF THE ACCESSIBILITY
 CODE COMPLYING WITH ASME A18.1. PLEASE PROVIDE THE
 MANUFACTURERS SPECIFICATION AND INSTALLATION
 INSTRUCTIONS.
  
 10) 2ND REQUEST. SHEET A-1 SHOWS THE LIFE SAFETY PLAN,
 PLEASE PROVIDE A FLOOR PLAN WITH ACTUAL LAYOUT OF
 ARTWORK, FURNITURE, TEMPORARY PARTITIONS FOR HANGING
 ART WORK AND OR KIOSK SHOW TRAVEL DISTANCES, AND COMMON
 PATH OF TRAVEL IT WOULD APPEAR THERE MAYBE ISSUES WITH
 COMMON PATH OF TRAVEL FROM THE NORTHWEST CORNER OF THE
 BUILDING. 2014 FBC-B TABLE 1014.3 AND TABLE 1016.2.
  
 11) 2ND REQUEST. SHEET A-1 THE ELEVATED MERCANTILE ART
 AREA ONLY SHOWS ONE MEANS OF EGRESS. FBC-B TABLE 1015.1
 & FBC-B 1015.2.1 REQUIRES 2 MEANS OF EGRESS WHEN THE
 OCCUPANT LOAD IS 50 OR MORE OCCUPANTS. ALTHOUGH THE
 ENTRY DOOR FROM NORTH RAILROAD AVENUE WOULD BE THE 2ND
 MEANS OF EGRESS, TO LEAVE FROM THE ELEVATED MERCANTILE
 ART AREA, ONE WOULD HAVE TO TRAVEL THROUGH THE DOUBLE
 DOORS AND THROUGH THE OFFICE AREA AND OUT THE EXIT DOOR
 ONTO THE SIDEWALK AT NORTH RAILROAD AVENUE.
  
 11A) COMPLIED, UNDER CURRENT DESIGN. THE DOUBLE DOORS
 AT THE OFFICE WOULD HAVE TO BE SWUNG AROUND TO COMPLY
 WITH 1008.1.2, DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHEN THE OCCUPANT LOAD IS GREATER THAN
 49.
  
 11B) 2ND REQUEST, THIS DOORWAY MAY STILL NEED TO BE
 CONSIDERED FOR THE 2ND EXIT. PLEASE PROVIDE THE
 DIFFERENCE IN HEIGHT BETWEEN THE CITY SIDEWALK AND THE
 BOTTOM LANDING OF THE STAIRWAY, THIS NEEDS TO BE PART
 OF AN ACCESSIBLE ENTRANCE/ EXIT. 2014 ACCESS. CODE
 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 THE PICTURES FROM GOOGLE STREET VIEW OF FEB. 2015 IT
 WOULD APPEAR THERE IS AT LEAST A 4 INCH DIFFERENCE IN
 HEIGHT FROM THE CITY SIDEWALK TO THE ENTRY DOOR FLOOR
 LEVEL.
  
 11C) NOTICE ONLY!!!! PLEASE NOTE THE EGRESS DOOR THAT
 OPENS ONTO NORTH RAILROAD AVENUE IS AN EXISTING
 NON-CONFORMING DOORWAY THAT SWINGS OUT OVER THE PUBLIC
 SIDEWALK, NOTE IF THE DOOR IS NOT REPLACED IT DOES NOT
 NEED TO BE REPLACED, BUT WHEN THE DOOR AND JAMB ARE
 REPLACED IT WILL STILL NEED TO SWING OUT BUT RECESSED
 BACK IN AN ALCOVE.
 2014 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8
 FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC
 RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN
 HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN
 SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS
 SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 11D) GOOGLE STREET VIEW OF FEB. 2015 SHOWS THE N.
 RAILROAD ENTRY DOOR, IT SEEMS TO BE NARROW, PLEASE
 PROVIDE HOW WIDE THIS DOOR ACTUALLY IS. 2014 FBC-B
 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH DOOR
 OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 11E) SEMI- COMPLIED. SHEET A3 SHOWS NEW STOREFRONT
 FRAMES. IN THE GOOGLE STREET VIEW SHOOT IN FEB. 2015
 PLEASE ALSO NOTE THE GARAGE DOORS ARE STILL IN THE
 OPENINGS AT THE LOADING BAYS, HOW CAN THE SUPPOSED
 EXISTING GUARDRAILS BE EXISTING? 107.2.1.3 ADDITIONAL
 INFORMATION WILL BE REQUIRED.
  
 12) 2ND REQUEST. SHEET A4 DOES NOT COMPLY WITH THE
 HANDRAIL NOR GUARDRAIL REQUIREMENTS. 2014 FBC-B
 1607.8.1 HANDRAILS AND GUARDS.
 HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A
 LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) IN
 ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL
 ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH SECTION
 2407.
  
 12A) 2014 FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS
 AND GUARDS SHALL ALSO BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 200 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 12B) 2014 FBC-B 1607.8.1.2 INTERMEDIATE RAILS.
 INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
 BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO RESIST
 A CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 12C) PLEASE DO NOT RESTATE THE CODE, BUT PROVIDE
 CALCULATIONS. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 12D) SHEETS A1 AND A2 DOES NOT SHOW A HANDRAIL FOR ANY
 OF THE EXISTING STAIRS OR FOR THE EXISTING (PROPOSED)
 STAIRS. 805.9 HANDRAILS. EXISTING BUILDING CODE. THE
 REQUIREMENTS OF SECTIONS EXIST. BUILD. CODE. 805.9.1
 AND 805.9.2 SHALL APPLY TO HANDRAILS FROM THE WORK AREA
 FLOOR TO, AND INCLUDING, THE LEVEL OF EXIT DISCHARGE.
  
 12D)(1)EXIST BUILD. CODE 805.9.1 MINIMUM REQUIREMENT.
 EVERY REQUIRED EXIT STAIRWAY THAT IS PART OF THE MEANS
 OF EGRESS FOR ANY WORK AREA AND THAT HAS THREE OR MORE
 RISERS AND IS NOT PROVIDED WITH AT LEAST ONE HANDRAIL,
 OR IN WHICH THE EXISTING HANDRAILS ARE JUDGED TO BE IN
 DANGER OF COLLAPSING, SHALL BE PROVIDED WITH HANDRAILS
 FOR THE FULL LENGTH OF THE RUN OF STEPS ON AT LEAST ONE
 SIDE. ALL EXIT STAIRWAYS WITH A REQUIRED EGRESS WIDTH
 OF MORE THAN 66 INCHES (1676 MM) SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 12D)(2) EXISTING BUILD. CODE 805.9.2 DESIGN. HANDRAILS
 REQUIRED IN ACCORDANCE WITH SECTION 805.9.1 SHALL BE
 DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 12E) GUARDRAILS SHALL BE 42 INCHES HIGH. 1013.3 HEIGHT.
  
 12F) HANDRAILS ON STAIRS NEEDS TO COMPLY WITH 2014
 FBC-B WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN
 FLIGHTS, THE HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP RISER AND
 CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE
 BOTTOM RISER.
  
 12G) SHEET A4 THERE IS A DETAIL OF AN ACCESSIBLE RAMP,
 MISSING INFORMATION INCLUDES STEEL RE-INFORCEMENT
 NEEDED FOR THE FOUNDATION AND UPRIGHT RETAINING WALL
 RE-INFORCEMENT AS WELL SIZE OF THE RE-BARS AND
 FREQUENCY IN PLACEMENT. 1-7.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 12H) SHEET A4 THERE IS A DETAIL OF AN ACCESSIBLE RAMP
 THERE IS NO DIMENSION AS TO THE WIDTH OF THE ACCESSIBLE
 RAMP, 2014 FBC-B 1010.6.1 WIDTH. THE MINIMUM WIDTH OF A
 MEANS OF EGRESS RAMP SHALL NOT BE LESS THAN THAT
 REQUIRED FOR CORRIDORS BY SECTION 1018.2.
  
 12I) 2014 FBC-B 1010.4 CROSS SLOPE. THE SLOPE MEASURED
 PERPENDICULAR TO THE DIRECTION OF TRAVEL OF A RAMP
 SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN 48 UNITS
 HORIZONTAL (2-PERCENT SLOPE).
  
 12J) 2014 FBC-B 1010.5 VERTICAL RISE. THE RISE FOR ANY
 RAMP RUN SHALL BE 30 INCHES (762 MM) MAXIMUM. A
 MID-LANDING WILL BE REQUIRED, PLEASE INDICATE THE
 MID-LANDING THE LANDING LENGTH SHALL BE 60 INCHES
 MINIMUM FBC-B 1010.7.3.
  
 13) THE PERMIT VALUE IS VERY LOW FOR THE WORK SHOWN ON
 THE PLANS AS WELL AS THE WORK THAT WAS DONE WITHOUT A
 PERMIT.
  
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 14) SHEET A4 PROVIDES THE WIND DESIGN CRITERIA AND
 PROVIDES PRESSURES FOR THE OVERALL OPENING, BUT DOES
 NOT INCLUDE THE PRESSURES THAT ARE GOING TO BE FOUND IN
 10 SQ. FT., 20 SQ. FT. NOR 50 SQ. FT. NOTE THE
 INDIVIDUAL GLAZING WILL HAVE HIGHER PRESSURES THAN THE
 OVERALL UNIT, THE SAME HOLDS TRUE FOR BOTH THE VERTICAL
 AND HORIZONTAL MULLIONS. WE ARE STILL MISSING THE
 PRESSURES FOR THE 10, 20 AND 50 SQ. FT. 2014 FBC-B
 COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2).
  
 14A) SHEET A4 UNDER THE WIND DESIGN LIST 3 REFERENCES
 TO THE 2014 RESIDENTIAL CODE R616.4, R703.1.3 AND TABLE
 R301.2(2), THESE ARE ALL TO BE USED WITH SINGLE FAMILY
 DWELLINGS, NOT TO BE USED WITH THE COMMERCIAL CODE,
 FBC-BUILDING CODE, SEE CHAPTER 1609.
  
 14B) SUBMIT PRODUCT APPROVALS: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 14C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 14D) SHEET A4 THE ACCESSIBLE THRESHOLD NEEDS TO COMPLY
 WITH: THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 14E) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  