Plan Review Notes
Plan Review Notes For Permit 17120517
Permit Number 17120517
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-08 12:11:211ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. C-1 AND P-2 THE PLUMBING FIXTURE REQUIREMENTS
 IS CONFUSING UNDER MERCANTILE THE CALCULATION IS 1WC
 PER 500 MEN AND WOMEN PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION,
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 609.4 POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
  
 5. PLEASE SHOW CLEAR FLOOR SPACE INCLUDING DIMENSIONS
 FOR THE WC, LAVATORY AND WATER FOUNTAIN. PER FBC ACC
 604.3.1, 606.2 AND 602.2
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PLEASE
 CLARIFY IF THE LAV WILL BE A WALLHUNG OR VANITY
 TYPE-LIKE DETAIL SHOWS.
  
 7. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 8. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 9. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR
  
 10. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.4 SPOUT
 HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 11. PROVIDE ENLARGED DETAIL FOR BOTH BATHROOMS. PER WPB
 AMEND TO FBC 107.2.1
  
 12. PLEASE SHOW COMPLIANCE WITH FBC PL 403.2 SEPARATE
 FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 13. THE EXISTING WATER CLOSET SHOULD BE VENTED BY
 EXITING LAVATORY. PER WPB AMEND TO FBC 107.2.1
  
 14. THE BRANCH DRAIN FOR THE WATER FOUNTAIN SHALL
 CONNECT DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL
 912.1
  
 15. THE BRANCH DRAIN FOR THE SERVICE SINK SHALL CONNECT
 DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 16. PROVIDE WATER ISOMETRIC DRAWING . PER WPB AEND TO
 FBC 107.3.5.1.3(13)
  
 17. SHOW LOCATION OF EXISTING WATER HEATER IF OVER 50'
 FROM FIXTURE A RECIRCULATION SYSTEM WILL BE REQUIRED.
 PER FBC PL 607.2
  
 18. IS THE WATER HEATER EXISTING TO REMAIN OR WILL IT
 BE REPLACED. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  