Plan Review Notes For Permit 17120517 |
Permit Number |
17120517 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-27 11:29:49 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | CODES | | PERMIT #17120517 | | 12/27/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET C-1: PLEASE CORRECT THE NOTE THAT IS EXCLUDING | | COMPLIANCE WITH THE FL. ENERGY CONSERVATION CODE. THE | | PROPOSED PROJECT IS NOT A RENOVATION, IT IS A CHANGE OF | | OCCUPANCY. REFER TO SECTION C101.4.4 AND SHOW | | COMPLIANCE. | | | | 2) SHEET M-1: EXHAUST VENTILATION IS REQUIRED FOR THE | | LOADING DOCK AND THE TRUCK PARKING GARAGE. REFER TO | | SECTIONS 404.1, 404.2, AND 404.3 AND SHOW COMPLIANCE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|