2018-01-02 13:38:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. LOAD CALCULATION PROVIDED USES DEMAND FACTORS FOR A |
| RESTAURANT, WHICH IS NOT PERMITTED FOR THIS PROJECT. |
| PROVIDE ACCURATE LOAD CALCULATION PER NEC. NEC 220 |
| 2. MAIN PANEL SHOWS TWO 200 AMP BREAKERS, ONE FEEDING |
| PANEL A AND ONE FEEDING PANEL B. THE RISER DIAGRAM |
| SHOWS THAT THESE PANELS ARE FED WITH CONDUCTOR SIZE |
| 1/0. CONDUCTOR SIZE 1/0 IS NOT RATED FOR 200 AMPS. |
| PROVIDE CORRECTION. NEC 310.15(B)(16) |
| 3. RISER DIAGRAM SHOWS THE 600 AMP MAIN PANEL BEING FED |
| WITH THREE 3/0 CONDUCTORS. CONDUCTOR SIZE 3/0 IS NOT |
| RATED FOR 600 AMPS. ALSO, THIS IS SHOWN AS A 3 PHASE |
| SERVICE, WHICH WOULD REQUIRE 4 WIRES FROM POWER |
| COMPANY. AN EGC (EQUIPMENT GROUNDING CONDUCTOR) WOULD |
| NOT BE INSTALLED IN THIS CONDUIT. PROVIDE CORRECTIONS |
| NEC 310.15(B)(16), 250.6; FBC 107.2.1 |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| AUTOMATIC CONTROL REQUIRED, INCLUDING EXTERIOR AREAS. |
| FBC EC 405.2.2, 405.2.2.2, 405.2.4 |
| 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| CODE. THIS SHOULD BE EXPRESSED IN LIGHT FIXTURE WATTAGE |
| IN RELATION TO SQUARE FOOT WATTAGE PERMITTED. IT HAS |
| NOTHING TO DO WITH THE AMPACITY OF THE CIRCUIT FEEDING |
| THE LIGHTING. FBC EC 405.5.2 |
| 7. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 |
| 8. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC 405.7.1 |
| 9. PROVIDE CONNECTION TO ALL GROUNDING ELECTRODES |
| PRESENT AT BUILDING. NEC 250.50 |
| 10. PER THE WPB AMENDMENTS TO THE FBC, 107.2.1.4 |
| QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. PROVIDE CORRECTION. |
| 11. PROVIDE SHOW WINDOW OUTLETS PER CODE. NEC 210.62 |
| 12. PROVIDE DEDICATED SIGN CIRCUIT WITH AUTOMATIC |
| CONTROL. NEC 600.5; FBC EC 405.2.4 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |