Plan Review Notes
Plan Review Notes For Permit 17120517
Permit Number 17120517
Review Stop B
Sequence Number 1
Notes
Date Text
2017-12-20 17:44:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120517/ CHANGE OF OCCUPANCY
 ADD: 925 N. RAILROAD AVE. (PCN:
 74-43-43-15-20-005-0110)
 CONT: FLORIDA GENERAL CONTRACTOR
 TEL: 561-704-5042
 E-MAIL: JIG3684@ YAHOO.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 20/ 2017
 ACTION: DENIED
  
 1) PLEASE CORRECT THE PERMIT AND PLAN ADDRESS. THE
 ADDRESS INDICATED ON BOTH THE PLANS AND PERMIT
 APPLICATION INDICATE 925 N RAILROAD AVE. PCN:
 74-43-43-15-20-005-0110. THE LOCATION OF THE BUILDING
 SHOWN ON SHEET C-1 IS LOCATED AT THE ADDRESS 1013 N.
 RAILROAD AVE. PCN: 74-43-43-15-20-005-0090. PLEASE
 CORRECT THE ADDRESS ON THE PERMIT APPLICATION AND
 PLANS. SHEET C-1 SHOWS THE SITE AS ONE PROPERTY,
 WHEREAS THERE IS 3 LOTS AND 3 ADDRESSES.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2A) DISCREPANCY IN AREA. SHEET C1 INDICATES THE SQUARE
 FOOT AREA OF THIS BUILDING AS 11,800 SQ. FT. IN
 MULTIPLE AREAS, WHEREAS THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE SHOWS 6525 SQ. FT. OF WAREHOUSE, 715
 SQ. FT. OF OFFICE AND A 2ND AREA OF WAREHOUSE OF 360
 SQ. FT. FOR A TOTAL OF 7600 SQ. FT. DISCREPANCY IN
 SQUARE FEET. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) DISCREPANCY IN AREA. SHEET C1 UNDER THE HEADING OF
 OCCUPANT LOAD INDICATES THE SQUARE FOOT AREA OF THIS
 BUILDING AS 8442 SQ. FEET, WHEREAS THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE SHOWS 6525 SQ. FT. OF
 WAREHOUSE, 715 SQ. FT. OF OFFICE AND A 2ND AREA OF
 WAREHOUSE OF 360 SQ. FT. FOR A TOTAL OF 7600 SQ. FT.
 DISCREPANCY IN SQUARE FEET. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET C1 THE COVERSHEET UNDER THE HEADING OF PROJECT
 DATA & OCCUPANT LOAD DOES NOT LIST TO WHAT CODE THIS
 PLAN WAS DESIGNED, NOR DOES THE PLAN INDICATE
 COMPLIANCE WITH THE REQUIREMENTS OF THE 2014 EXISTING
 BUILDING CODE CHAPTER 10 FOR CHANGE IN OCCUPANCY. THE
 2014 FLORIDA BUILDING CODE AND EXISTING BUILDING CODE
 WAS ENACTED STATEWIDE ON JUNE 30/ 2015.
  
 4) 2014 FBC-EXISTING BUILDING CODE 1001.3 CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP.
  
 5) SHEET A-1 TOWARD THE SOUTH SIDE OF THE BUILDING THE
 PLANS STATE THAT THERE IS AN EXISTING 2 HOUR, 8 INCH
 CMU FIRE SEPARATION WALL TO REMAIN, EXISTING ADJACENT
 PROPERTY COURTYARD. PLEASE NOTE THE PALM BEACH COUNTY
 PROPERTY APPRAISERS ARIELS SHOW THE PROPERTY LINE JUST
 ADJACENT TO THE 2 HOUR RATED EXTERIOR WALL.
 THIS MEANS THE SOUTH EXIT, ELEVATED DECK, LOADING DOCK
 AND PROPOSED NEW ADA LIFT IS ON A DIFFERENT LOT,
 PCN: 74-43-43-15-20-005-0110 ADDRESSED 925 N. RAILROAD
 AVE. IT WOULD APPEAR A UNITY OF TITLE WOULD BE REQUIRED
 TO ALLOW FOR OPENINGS IN THE SOUTH WALL AND ALLOWING
 EXITING ONTO THE LOT ADDRESSED 925 N. RAILROAD AVE.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
  
 6) NETHER SHEET A-1 NOR A-2 PROVIDE WHAT IS EXISTING
 AND WHAT IS NEW. PLEASE BE ADVISED GOOGLE STREET VIEW
 IN FEB. OF 2015 SHOWS THE 4 LOADING BAYS OPEN ALONG N.
 RAILROAD AVE. FOR 925 AND 1013 N. RAILROAD AVE. WITHIN
 THE LOADING BAYS THERE IS ONLY ONE EXISTING SET OF
 STAIR AND NO GUARDRAILS. THE OTHER ISSUE IS HOW THE
 BUILDINGS ARE BUILT BETWEEN 925 AND 1013 N. RAILROAD
 AVE. THERE WOULD HAVE BEEN A 4 HOUR FIRE WALL
 SEPARATING THE BUILDINGS, WE DO NOT HAVE PERMITS PULLED
 CREATING OPENINGS WITHIN THE 4 HOUR FIRE WALL NOR HOW
 THE STRUCTURE ABOVE IS BEING SUPPORTED? IT WOULD APPEAR
 THERE HAS BEEN A LOT OF WORK ALREADY COMPLETED WITHOUT
 THE BENEFIT OF A PERMIT. A THOROUGH REVIEW CANNOT BE
 MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW. WORK COMPLETED
 WITHOUT THE BENEFIT OF A PERMIT MAY ALSO RESULT IN A 4X
 FEE FOR THE WORK NOT PERMITTED.
 7) SHEET A-1 SHOWS THE EXIT ACCESS PATHS THROUGHOUT THE
 BUILDING BUT THE TRAVEL DISTANCE FOR EACH ROUTE HAS NOT
 BEEN INDICATED ON THE PLANS, PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-B TABLE 1016.2.
  
 8) THE COVERSHEET INDICATES THE OCCUPANT LOAD OF 302
 AND SHEET A-1 SHOWS 2 EXITS AND ONLY 1 ACCESSIBLE EXIT.
 PLEASE REVIEW SECTION:
  
 2014 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 2014 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404.
  
 (GRAY BOX FLORIDA SPECIFIC). BARRIERS AT COMMON OR
 EMERGENCY ENTRANCES AND EXITS OF BUSINESS
 ESTABLISHMENTS CONDUCTING BUSINESS WITH THE GENERAL
 PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION, OR UNDER
 CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT A PERSON
 FROM USING SUCH ENTRANCES OR EXITS SHALL BE REMOVED.
  
 9) SHEET A-1 INDICATES THE USE OF (2) NEW LIFTS, PLEASE
 BE MORE SPECIFIC, TO BE LIMITED USE/ LIMITED-
 APPLICATION UNDER SECTION 408 OF THE ACCESSIBILITY CODE
 COMPLYING WITH ASME A17.1 OR PLATFORM LIFTS UNDER
 SECTION 410 OF THE ACCESSIBILITY CODE COMPLYING WITH
 ASME A18.1. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATION AND INSTALLATION INSTRUCTIONS.
  
 10) SHEET A-1 SHOWS THE LIFE SAFETY PLAN, PLEASE
 PROVIDE A FLOOR PLAN WITH ACTUAL LAYOUT OF ARTWORK,
 FURNITURE, TEMPORARY PARTITIONS FOR HANGING ART WORK
 AND OR KIOSK SHOW TRAVEL DISTANCES, AND COMMON PATH OF
 TRAVEL IT WOULD APPEAR THERE MAYBE ISSUES WITH COMMON
 PATH OF TRAVEL FROM THE NORTHWEST CORNER OF THE
 BUILDING. 2014 FBC-B TABLE 1014.3 AND TABLE 1016.2.
  
 11) SHEET A-1 THE ELEVATED MERCANTILE ART AREA ONLY
 SHOWS ONE MEANS OF EGRESS. FBC-B TABLE 1015.1 REQUIRES
 2 MEANS OF EGRESS WHEN THE OCCUPANT LOAD IS 50 OR MORE
 OCCUPANTS. ALTHOUGH THE ENTRY DOOR FROM NORTH RAILROAD
 AVENUE WOULD BE THE 2ND MEANS OF EGRESS, TO LEAVE FROM
 THE ELEVATED MERCANTILE ART AREA, ONE WOULD HAVE TO
 TRAVEL THROUGH THE DOUBLE DOORS AND THROUGH THE OFFICE
 AREA AND OUT THE EXIT DOOR ONTO THE SIDEWALK AT NORTH
 RAILROAD AVENUE.
  
 11A) THE DOUBLE DOORS AT THE OFFICE WOULD HAVE TO BE
 SWUNG AROUND TO COMPLY WITH 1008.1.2, DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHEN THE OCCUPANT
 LOAD IS GREATER THAN 49.
  
 11B) PLEASE PROVIDE THE DIFFERENCE IN HEIGHT BETWEEN
 THE CITY SIDEWALK AND THE BOTTOM LANDING OF THE
 STAIRWAY, THIS NEEDS TO BE PART OF AN ACCESSIBLE
 ENTRANCE/ EXIT. 2014 ACCESS. CODE 206.4.1 PUBLIC
 ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2
 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC
 ENTRANCES SHALL COMPLY WITH 404.
 THE PICTURES FROM GOOGLE STREET VIEW OF FEB. 2015 IT
 WOULD APPEAR THERE IS AT LEAST A 4 INCH DIFFERENCE IN
 HEIGHT FROM THE CITY SIDEWALK TO THE ENTRY DOOR FLOOR
 LEVEL.
  
 10C) NOTICE ONLY!!!! PLEASE NOTE THE EGRESS DOOR THAT
 OPENS ONTO NORTH RAILROAD AVENUE IS AN EXISTING
 NON-CONFORMING DOORWAY THAT SWINGS OUT OVER THE PUBLIC
 SIDEWALK, NOTE IF THE DOOR IS NOT REPLACED IT DOES NOT
 NEED TO BE REPLACED, BUT WHEN THE DOOR AND JAMB ARE
 REPLACED IT WILL STILL NEED TO SWING OUT BUT RECESSED
 BACK IN AN ALCOVE.
 2014 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8
 FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC
 RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN
 HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN
 SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS
 SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 10D) GOOGLE STREET VIEW OF FEB. 2015 SHOWS THE N.
 RAILROAD ENTRY DOOR, IT SEEMS TO BE NARROW, PLEASE
 PROVIDE HOW WIDE THIS DOOR ACTUALLY IS. 2014 FBC-B
 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH DOOR
 OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 10E) IN THE GOOGLE STREET VIEW SHOOT IN FEB. 2015
 PLEASE ALSO NOTE THE GARAGE DOORS ARE STILL IN THE
 OPENINGS AT THE LOADING BAYS, HOW CAN THE SUPPOSED
 EXISTING GUARDRAILS BE EXISTING? 107.2.1.3 ADDITIONAL
 INFORMATION WILL BE REQUIRED.
  
 11) SHEET A1 & A2 BOTH WILL NEED TO SHOW COMPLIANCE
 WITH HANDRAILS AND GUARDRAILS MEETING ALL (3) SECTIONS
 OF CODE.
 2014 FBC-B 1607.8.1 HANDRAILS AND GUARDS.
 HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A
 LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) IN
 ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL
 ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH SECTION
 2407.
  
 11A) 2014 FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS
 AND GUARDS SHALL ALSO BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 200 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 11B) 2014 FBC-B 1607.8.1.2 INTERMEDIATE RAILS.
 INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
 BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO RESIST
 A CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 11C) PLEASE DO NOT RESTATE THE CODE, BUT PROVIDE
 CALCULATIONS. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 11D) SHEETS A1 AND A2 DOESN?T SHOW A HANDRAIL FOR ANY
 OF THE EXISTING STAIRS OR FOR THE EXISTING (PROPOSED)
 STAIRS. 805.9 HANDRAILS. EXISTING BUILDING CODE. THE
 REQUIREMENTS OF SECTIONS 805.9.1 AND 805.9.2 SHALL
 APPLY TO HANDRAILS FROM THE WORK AREA FLOOR TO, AND
 INCLUDING, THE LEVEL OF EXIT DISCHARGE.
  
 11D)(1) 805.9.1 MINIMUM REQUIREMENT. EVERY REQUIRED
 EXIT STAIRWAY THAT IS PART OF THE MEANS OF EGRESS FOR
 ANY WORK AREA AND THAT HAS THREE OR MORE RISERS AND IS
 NOT PROVIDED WITH AT LEAST ONE HANDRAIL, OR IN WHICH
 THE EXISTING HANDRAILS ARE JUDGED TO BE IN DANGER OF
 COLLAPSING, SHALL BE PROVIDED WITH HANDRAILS FOR THE
 FULL LENGTH OF THE RUN OF STEPS ON AT LEAST ONE SIDE.
 ALL EXIT STAIRWAYS WITH A REQUIRED EGRESS WIDTH OF MORE
 THAN 66 INCHES (1676 MM) SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 11D)(2) 805.9.2 DESIGN. HANDRAILS REQUIRED IN
 ACCORDANCE WITH SECTION 805.9.1 SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 12) THE PERMIT VALUE IS VERY LOW FOR THE WORK SHOWN ON
 THE PLANS AS WELL AS THE WORK THAT WAS DONE WITHOUT A
 PERMIT.
  
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER