Plan Review Notes For Permit 17120453 |
Permit Number |
17120453 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-01-03 17:14:45 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17120453 | | 1/3/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M1: PLEASE CLARIFY HOW AIR IS BEING RETURNED | | FROM BEDROOMS 1 & 2. | | | | 2) M-1: PLEASE CLARIFY IF THE DUCT SHAFTS BY THE | | ELEVATOR ARE FIRE-RATED SHAFTS. PLEASE NOTE FIRE | | DAMPERS MAY BE REQUIRED FOR DUCT PENETRATIONS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|