Plan Review Notes
Plan Review Notes For Permit 17120419
Permit Number 17120419
Review Stop G
Sequence Number 2
Notes
Date Text
2018-01-04 08:05:412ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
 I SUGGEST A MEETING BE SET UP TO EXPEDITE APPROVAL OF
 THIS REVISION MY CONTACT INFO IS BELOW.
  
 1. THE APPROVED SET OF DRAWINGS WAS SIGNED AND SEALED
 BY DESIGN PROFESSIONAL ANY REVISIONS SHALL BE SIGNED
 AND SEALED BY THE SAME DESIGN PROFESSIONAL. PER WPB
 AMEND TO FBC 107.2 AND FS 61G15-23.003
  
 2. PLEASE PROVIDE REVISED FLOOR PLAN SHT. P.1. PER WPB
 AMEND TO FBC 107.2.1
  
 NEW COMMENT:
  
 1. PER FBC FG TABLE 402.4(2) YOUR DEVELOPED LENGTH
 WOULD BE ROUNDED UP TO 30' AND MAX BTU LOAD FOR 1" PIPE
 IS 374,000 WHICH MAKES YOUR FIRST SECTION OF PIPE
 UNDERSIZED. IT SHALL BE 11/4" TO ALLOW FOR A BTU LOAD
 OVER 374,000.
  
 2. ON THE ORIGINAL SET OF PLANS IT SHOWS THE TANKLESS
 HEATER WITH A MAX BTU LOAD OF 199,000 THE REVISED
 DRAWING SHOWS IT AT 190,000. PLEASE PROVIDE THE
 MANUFACTURE SPECIFICATIONS OF ALL THE GAS APPLIANCES TO
 MORE ACCURATELY CALCULATE THE BTU LOAD OF THE SYSTEM.
 PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE A RISER DIAGRAM THAT SHOWS THE LENGTH OF OF
 EACH CUT SECTION OF PIPE TO MORE ACCURATELY CALCULATE
 THE BTU LOAD OF THE SYSTEM. PER WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  