2017-12-16 11:47:03 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE APPROVED SET OF DRAWINGS WAS SIGNED AND SEALED |
| BY DESIGN PROFESSIONAL ANY REVISIONS SHALL BE SIGNED |
| AND SEALED BY THE SAME DESIGN PROFESSIONAL. PER WPB |
| AMEND TO FBC 107.2 AND FS 61G15-23.003 |
| |
| 2. PLEASE PROVIDE REVISED FLOOR PLAN SHT. P.1. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 3. THE TOTAL DEVELOPED LENGTH IS STATED AS 18' YET THE |
| LAST SECTION OF PIPE TO THE DRYER IS LABELED AS 18' |
| PLEASE LABEL ALL SECTIONS OF PIPE INCLUDING THE FIRST |
| SECTION FROM THE METER AND THEY SHALL MATCH THE TOTAL |
| DEVELOPED LENGTH. PER WPB AMEND TO FBC 107.2.1 |
| |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) AND TYPE OF |
| GAS, (LP OR NATURAL).PER FBC-2014 FUEL GAS SEC. 402.2. |
| IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 5. PLEASE PROVIDE TABLE THAT WAS USED FOR SIZING |
| SYSTEM. PER FBC FG 402.4 |
| |
| 6. SHOW SHUT OFF VALVE FOR COOK TOP ON THE BRANCH |
| CONNECTING APPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7. SHOW THE REQUIRED DIRT LEG ON THE SYSTEM. PER FBC FG |
| 408.4 |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |