Notes |
Date |
Text |
2018-06-01 16:42:57 | 06/01/2018 2ND PLUMBING REVIEW**DENIED** | | | | 1) CONSTRUCTION DOCUMENTS SHALL BE DRAWN ON AND WITH | | SUITABLE MATERIAL. NO PENCIL IS ALLOWED. FBC 107.2.1 | | | | 2) PROVIDE AN ISOMETRIC DRAWING SHOWING PIPE SIZE AT | | EACH SECTION TO COMPLY WITH FBC 107.3.5 YOU ARE ONLY | | SHOWING THE RAN FROM THE HAND SINK AND THE VENT FROM | | THE FLOOR SINK. | | | | 3) YOUR SHOWING 2? AT THE INDIRECT WASTE FLOOR SINK | | WHICH IS UNDERSIZED AS 3? IS REQUIRED AS YOU HAVE 8 | | DRAINAGE FIXTURE UNITS (DFU?S) . SEE FBC P TABLE | | 710.1(2) | | | | SEE INTERCETOR PLAN REVIEW FOR ADDED NOTES. | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | | | |
|