Plan Review Notes For Permit 17120398 |
Permit Number |
17120398 |
|
Review Stop |
P-GREASE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-01 16:49:56 | 06/01/2018 1ST REVIEW PLUMBING INTERCEPTOR**DENIED** | | | | | | 1) YOU MUST SHOW HOW YOU SIZED THE INTERCEPTOR IN | | ACCORDANCE WITH RULE 64E-6 FL. AMEND CODE. | | | | 2) THE INTERCEPTOR MODEL YOU HAVE SUPPLIED IS TOO SMALL | | BASE ON MY CALCULATIONS FROM RULE 64E-6 FL. AMEND CODE. | | PROVIDE ANSWER TO COMMENT 1 AND VERIFY BASED ON MODEL | | SPEC'S. FBC 107.2.1 | | | | 3) A SEPERATE PERMIT APPLICATION FOR GREASE | | INTERCEPTERS IS REQUIRED AND CAN BE PULLED AS A SUB | | PERMIT FROM THIS MASTER. FBC 105.1, FBC P 1003.2 | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|