Plan Review Notes For Permit 17120347 |
Permit Number |
17120347 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-01-08 06:52:56 | 1) THE DESIGN PROFESSIONAL OF RECORD SHALL INDICATE ON | | SHEET #1 OF 3 THAT THIS IS A CHANGE OF OCCUPANCY AND | | NOTE THE PREVIOUS OCCUPANCY OF THE SPACE AND THE NEW | | OCCUPANCY OF THE SPACE. 2014 FBC EXISTING BUILDING CODE | | CHAPT. 501.3, AND SEC. 1001.3. | | 2) THE HANDWASH SINK AND THE HAIRWASH SINKS ARE NOT | | PERMITTED ON A HORIZONTAL WET VENT PER 2014 | | FBC-PLUMBING SECD. 912.1. AN INDIVIDUAL VENT ON THE MOP | | SINK WILL RECTIFY THIS ISSUE. | | 3) THE UNDERGROUND HORIZONTAL SANITARY DRAIN FOR THE | | MOP SINK, HAIR SINKS AND HANDWASHING SINK SHALL BE A | | MINIMUM OF 3 INCHES UP TO THE FIRST HAIR SINK. 2014 | | FBC-PLUMBING SEC. 710.1 AND TABLE 710.1 (2). | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|