Plan Review Notes
Plan Review Notes For Permit 17120347
Permit Number 17120347
Review Stop P
Sequence Number 2
Notes
Date Text
2018-01-08 06:52:561) THE DESIGN PROFESSIONAL OF RECORD SHALL INDICATE ON
 SHEET #1 OF 3 THAT THIS IS A CHANGE OF OCCUPANCY AND
 NOTE THE PREVIOUS OCCUPANCY OF THE SPACE AND THE NEW
 OCCUPANCY OF THE SPACE. 2014 FBC EXISTING BUILDING CODE
 CHAPT. 501.3, AND SEC. 1001.3.
 2) THE HANDWASH SINK AND THE HAIRWASH SINKS ARE NOT
 PERMITTED ON A HORIZONTAL WET VENT PER 2014
 FBC-PLUMBING SECD. 912.1. AN INDIVIDUAL VENT ON THE MOP
 SINK WILL RECTIFY THIS ISSUE.
 3) THE UNDERGROUND HORIZONTAL SANITARY DRAIN FOR THE
 MOP SINK, HAIR SINKS AND HANDWASHING SINK SHALL BE A
 MINIMUM OF 3 INCHES UP TO THE FIRST HAIR SINK. 2014
 FBC-PLUMBING SEC. 710.1 AND TABLE 710.1 (2).
  