2018-03-05 17:01:10 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #17120347 |
| 3/5/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED. I HAVE |
| COPIED THEM BELOW- PLEASE COMPLY. |
| |
| |
| 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17120347 |
| 1/12/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| |
| 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. SEE |
| REQUIREMENTS BELOW: |
| |
| A) THE MAIN MECHANICAL REQUIREMENT FOR A HAIR SALON IS |
| AN EXHAUST VENTILATION SYSTEM THAT HAS AN EXHAUST RATE |
| OF 0.6 CFMS PER SQ. FT FOR THE SALON AREA- TABLE 403.3 |
| |
| B) THE EXHAUST FAN MUST BE SUPPLIED WITH A SOURCE OF |
| MAKEUP AIR AND MUST RUN CONTINUOUSLY WHENEVER THE SALON |
| IS IN OPERATION- SECTION 501.4 |
| |
| C) THE EXISTING OR NEW AC SYSTEM(S) MUST BE ABLE TO |
| PROVIDE OUTDOOR AIR TO OCCUPANTS AT A RATE OF 20 CFMS |
| PER PERSON AND 0.12 CFMS PER SQ. FT. THE OCCUPANT LOAD |
| PER THE MECHANICAL CODE IS CALCULATED AT 25 |
| PERSONS/SQ.FT.. PLEASE PROVIDE VENTILATION |
| CALCULATIONS. |
| |
| D) PLEASE NOTE IT IS PROHIBITED FOR AIR THAT IS |
| SUPPLIED TO THE SALON SPACE TO BE RECIRCULATED TO OTHER |
| ROOMS OR SPACES IN THE TENANT SPACE OR IN THE BUILDING |
| IN GENERAL- TABLE 403.3 FOOTNOTE B. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |