2018-03-06 16:02:15 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS NOT ADDRESSED: |
| |
| 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 4. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC |
| 600.5; FBC EC 405.2.4 |
| 5. PROVIDE SHOW WINDOW OUTLETS PER CODE. NEC 210.62 |
| 6. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. FBC EC 405.2.2, |
| 405.2.2.2 |
| |
| NEW COMMENT: |
| |
| 7. PLEASE BE ADVISED THAT THESE COMMENT HAVE NOT BEEN |
| ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF |
| IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD |
| TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS |
| REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO |
| EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |