Plan Review Notes
Plan Review Notes For Permit 17120347
Permit Number 17120347
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-15 09:26:27***CORRECTIONS***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE PREVIOUS REVIEW PASSED WITH PROVISO TO REVISE
 THE PLAN. IT IS NOT CLEAR WHY THIS WAS NOT DONE. AS THE
 PLAN MUST BE RESUBMITTED TO ADDRESS COMMENTS FROM OTHER
 TRADES, PLEASE REVISE PLAN AT THIS TIME.
  
 PLAN IS TO BE REVISED TO SHOW COMPLIANCE WITH FBC
 EXISTING BUILDING CHAPTER 10, CHANGE OF OCCUPANCY.
 STATE EXISTING OCCUPANCY, PROPOSED NEW, AND THEN SHOW
 COMPLIANCE WITH FOLLOWING:
 FBC EXISTING BUILDING TABLE 1012.4
 FBC EXISTING BUILDING TABLE 1012.5
 FBC EXISTING BUILDING TABLE 1012.6
  
 2. SALES COUNTER TO COMPLY WITH FBC ACCESSIBILILTY 904;
 PROVIDE A DETAIL.
  
 3. A LICENSED CONTRACTOR IS REQUIRED TO OVERSEE THIS
 PROJECT. THIS CONTRACTOR TAKES RESPONSIBILITY FOR AND
 SUPERVISES THE SUBCONTRACTORS. AT THIS TIME, THIS
 PERMIT APPLICATION IS A PLUMBING APPLICATION. A
 CONTRACTOR LICENSED TO OVERSEE THE WORK SHOULD BE THE
 PRIME CONTRACTOR. IS IT APPLICANT'S INTENT THAT
 PLUMBING CONTRACTOR IS THE PRIME CONTRACTOR? IF YES,
 HAVE THE PLUMBING CONTRACTOR CONTACT ME. IF NO, SUBMIT
 A PERMIT APPLICATION FROM THE GENERAL OR BUILDING
 CONTRACTOR WHO WILL BE THE CONTRACTOR SUPERVISING THIS
 PROJECT.
  
  
  
  
  