2017-12-19 06:13:47 | 1) CITY RECORDS SHOW THAT THE PREVIOUS BUSINESS IN THIS |
| SPACE WAS A RETAIL STORE (MERCANTILE OCCUPANCY) . A |
| HAIR SALON IS CONSIDERED A BUSINESS OCCUPANCY IN |
| ACCORDANCE WITH THE 2014 FBC-BUILDING SEC.304.1. |
| COMPLIANCE WITH THE 2014 FBC-EXISTING BUILDING SECS. |
| 1001.3 IS REQUIRED. |
| 2) 2014 FBC-EXISTING BUILDING VOLUME - SEC.1006.1 - |
| ACCESSIBILITY - ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| CODE, ACCESSIBILITY. THE EXISTING TOILET ROOM SHALL |
| COMPLY WITH THE REQUIREMENTS OF THE ACCESSIBILITY CODE. |
| SUBMIT A FLOOR PLAN SHOWING COMPLIANCE. |
| 3) CORRECT THE ADDRESS ON THE PLANS. THE PLANS NOTE THE |
| ADDRESS AS 118 CLEMATIS ST. AND THE ADDRESS ON THE |
| PERMIT APPLICATION IS LISTED AS 330 CLEMATIS ST., UNIT |
| #118. CLARIFY. |
| 4) SUBMIT A WATER RISER DIAGRAM THAT CLEARLY SHOWS THE |
| ENTIRE SCOPE OF WATER PIPING TO BE INSTALLED. WPB |
| AMEND. TO FBC SEC. 107.3.5.1.3 ( 3 ). |
| 5) SUBMIT A SANITARY RISER DIAGRAM THAT CLEARLY SHOWS |
| THE ENTIRE SCOPE OF DRAINAGE PIPING TO BE INSTALLED. |
| WPB AMEND. TO FBC SEC. 107.3.5.1.3 ( 4 ).SHOW ALL PIPE |
| SIZES ON THE SANITARY RISER. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 6) ALL INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN |
| DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 54 INCHES IN |
| TOTAL DEVELOPED LENGTH SHALL BE TRAPPED. 2014 |
| FBC-PLUMBING SEC. 802.2. |
| 7) THE SUBMITTED PLANS HAVE A NOTE STATING THAT THE |
| EXISTING PLUMBING FIXTURES IN THE TOILET ROOM ARE TO BE |
| REMOVED AND TO SEE SHEET TWO OF THREE FOR THE NEW |
| LAYOUT. THERE ARE NO SHEETS TWO OF THREE OR THREE OF |
| THREE AND THERE IS NO OTHER INFORMATION AS TO THE |
| INSTALLATION OF NEW FIXTURES OR WHAT ELSE WILL BE DONE. |
| CLARIFY. A MINIMUM OF ONE TOILET ROOM COMPLYING WITH |
| THE FLORIDA ACCESSIBILITY CODE SHALL BE PROVIDED. |
| 8) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE NEW |
| WASH STATION SINKS AND TO THE HAND SINK PER 2014 |
| FBC-PLUMBING SEC. 607.1. |
| 9) TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER |
| TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| AND SHALL LIMIT THE TEMPERED WATER TO A MAXIMUM OF 110 |
| DEGREES. 2014 FBC-PLUMBING SEC.607.1.2. |
| 10) MEANS SHALL BE PROVIDED FOR CONTROLLING INCREASED |
| PRESSURE CAUSED BY THERMAL EXPANSION IN ACCORDANCE WITH |
| 2014 FBC-PLUMBING SEC.607.3. |
| 11) SHOW THE OCCUPANT LOAD FOR THE NEW OCCUPANCY ON THE |
| PLANS. WPB AMEND. TO FBC SEC. 107.2.1. WPB AMEND. TO |
| FBC SEC. 107.3.5.1.1. |
| 12) BUILDINGS UNDERGOING A CHANGE OF OCCCUPANCY SHALL |
| ALSO COMPLY WITH THE 2014 FBC - EXISTING BUILDING CODE |
| CHAPTERS 7,8, & 9 PER 2014 FBC EXISTING BUILDING |
| SEC.1012.1.1. |
| |
| |