Plan Review Notes For Permit 17120337 |
Permit Number |
17120337 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-20 16:13:34 | | | | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | NOTE: PROVIDE INFORMATION PRIOR TO INSPECTIONS TO AVOID | | CONFLICTS/DELAYS | | | | 1- PROPOSED CABANA: SHOW COMPLIANCE WITH THE HEATING | | REQUIREMENTS OF SEC. R303.9 FBC-RESIDENTIAL. NOTE: | | SHEET E-1 SHOW AN EXISTING A/C UNIT TO BE RELOCATED | | ABOVE THE DOUBLE FRENCH DOORS. PROVIDE DETAIL SHOWING | | HOW THE RELOCATED A/C UNIT IS GOING TO BE INSTALLED | | ABOVE THE NEW FRENCH DOORS. IT DOESN'T SEEM TO BE | | ENOUGH ROOM. | | | | 2- THE HANDRAILS WERE REMOVED. HANDRAILS CAN NOT BE | | REMOVED. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS AS | | REQUIRED BY SEC. R311.7.8-RESIDENTIAL. |
|