2018-01-10 13:47:40PASSED ON MASTER#17120255
2017-12-27 11:07:021) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 FOR THE GAS REGULATOR TO BE INSTALLED. REGULATORS
 INSTALLED ON THE EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 USE. 2014 FGC SEC.410.1.
 2) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200
 PER THE FGC SEC. 616.1. THIS IS SHOWN AS AN OPTION IN
 THE GENERATOR SPECIFICATIONS. CLARIFY.
 3) SHT.P0.1- NOTE #7 - THE TRACER WIRE SHALL BE NOT IN
 CONTACT WITH THE PE PIPE. FGC SEC.404.17.3.
 4) SHOW THE DISTANCE FROM THE OUTLET OF THE METER TO
 THE MOST REMOTE LINE PRESSURE REGULATOR ON THE 2 PSI
 SYSTEM.2014 FGC SEC.402.4.3.
 5) THE BTU LOAD OF THE GENERATOR AT 60HZ IS 757,000
 BTU'S AT 100% LOAD ACCORDING TO THE MANUFACTURER'S
 SPECIFICATIONS BUT THE GAS DRAWING SHOWS THE BTU LOAD
 AS 699,000 BTU'S. CLARIFY.
  